Set up geothermal radiant heat – Honeywell PRESTIGE THX9321 User Manual

Page 101

Advertising
background image

THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

101

68-0311—02

Fossil Fuel Backup Heat (Backup Heat NOT

Allowed to Run with Heat Pump)

HEAT MODE

The thermostat turns on Backup Heat only when the indoor

temperature drops to the selected Backup Heat Differential

setting or the Backup Heat Upstage Timer expires (whichever

occurs first). Geothermal Forced Air Heat turns off when the

Backup Heat turns on. Geothermal Radiant Heat stays on

when the Backup Heat turns on.

EM. HEAT MODE

The thermostat turns on the Backup Heat to maintain the

desired temperature setting. Geothermal Radiant Heat and

Geothermal Forced Air Heat are not used.

Set Up Geothermal Radiant Heat

1. Select Geothermal Radiant Heat as shown in Fig. 199.

Fig. 199.

2. Select the number of Radiant Heat Stages. See Fig. 200.

Fig. 200.

3. Select the universal terminals wired to the Geothermal

Radiant Heat. See Fig. 201.

Fig. 201.

4. Select the Geothermal Radiant Heat Options. For exam-

ple: If this zone is Geothermal Radiant Heat only – select

None. See Fig. 202.

Fig. 202.

5. Select the Reversing Valve. See Fig. 203.

Fig. 203.

6. Select the number of Compressor and Backup Heat

Stages. See Fig. 204.

Fig. 204.

7. Select the Backup Heat Type. See Fig. 205.

Fig. 205.