THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

68-0311—02

138

EIM Wiring Diagrams

Typical wiring of a conventional system with up to 3-stage heat and 2-stage cool with one transformer.

Fig. 319. EIM wiring guide — conventional systems.

1 See guides on following pages for thermostat wiring and geothermal radiant heat wiring.
2 Wire a maximum of 4 sensors using the S1-S4 terminals. S1-S4 terminals can be connected to an indoor sensor, outdoor sen-

sor, discharge sensor, return sensor, dry contact device to display an alert or an occupancy sensor for remote setback.

3 Remove jumper(s) if using separate transformers.
4 See “Economizer Module Wiring Diagrams” beginning on page 151.
5 Connect wireless adapter to ABCD for extended wireless range.

HEAT STAGE 1

HEAT STAGE 2

HEAT STAGE 3

FAN

TO THERMOSTAT

STATUS

LEDS

JUMPERS

SENSORS

CONV

FURNACE

R
C

W

W2
W3

G

Y2

Y

TRANSFORMER

120

VAC

24

VAC

COMPRESSOR

STAGE 1

COMPRESSOR

STAGE 2

POWER

HEAT

COOL

FAN

U1
U2
U3

A

CONNECT OPTIONAL

SENSORS TO

S1 AND S2 TERMINALS

S4

S4

S3

S3

CONNECT OPTIONAL

SENSORS TO

S3 AND S4 TERMINALS

A

B

C

D

EIM

2

3

1

4

2

5