background image

THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

47

68-0311—02

4120

Residential:

Entry / Exit Remote

- Home Heat

Setpoint

Commercial:

Entry / Exit Remote

- Occupied Heat

Setpoint

None
40° F to 90° F

Note: setpoint is limited based on

setting at ISU 4100.

70° F

Both

No

The thermostat maintains this Heat setting

when the user presses Home / Occupied at

the Entry / Exit Remote. Select None to

delete this temperature setting. The

thermostat only responds to the Entry / Exit

Remote if a temperature is pre-set at this

screen. See “Wireless Entry/Exit Remote”

beginning on page 128.

4130

Residential:

Entry / Exit Remote

- Away Cool

Setpoint

Commercial:

Entry / Exit Remote

- Unoccupied Cool

Setpoint

None
50° F to 99° F

Note: setpoint is limited based on

setting at ISU 4100.

78° F

Both

No

The thermostat maintains this Cool setting

when the user presses Away / Unoccupied

at the Entry / Exit Remote. Select None to

delete this temperature setting. The

thermostat only responds to the Entry / Exit

Remote if a temperature is pre-set at this

screen. See “Wireless Entry/Exit Remote”

beginning on page 128.

4130

Residential:

Entry / Exit Remote

- Away Heat

Setpoint

Commercial:

Entry / Exit Remote

- Unoccupied Heat

Setpoint

None
40° F to 90° F

Note: setpoint is limited based on

setting at ISU 4100.

65° F

Both

No

The thermostat maintains this Heat setting

when the user presses Away / Unoccupied

at the Entry / Exit Remote. Select None to

delete this temperature setting. The

thermostat only responds to the Entry / Exit

Remote if a temperature is pre-set at this

screen. See “Wireless Entry/Exit Remote”

beginning on page 128.

4140

Residential:

Entry / Exit Remote

- Vacation Cool

Setpoint

Commercial:

Entry / Exit Remote

- Holiday Cool

Setpoint

None
50° F to 99° F

Note: setpoint is limited based on

setting at ISU 4100.

82° F

Both

No

The thermostat maintains this Cool setting

when the user presses Vacation / Holiday at

the Entry / Exit Remote. Select None to

delete this temperature setting. The

thermostat only responds to the Entry / Exit

Remote if a temperature is pre-set at this

screen. See “Wireless Entry/Exit Remote”

beginning on page 128.

4140

Residential:

Entry / Exit Remote

- Vacation Heat

Setpoint

Commercial:

Entry / Exit Remote

- Holiday Heat

Setpoint

None
40° F to 90° F

Note: setpoint is limited based on

setting at ISU 4100.

60° F

Both

No

The thermostat maintains this Heat setting

when the user presses Vacation / Holiday at

the Entry / Exit Remote. Select None to

delete this temperature setting. The

thermostat only responds to the Entry / Exit

Remote if a temperature is pre-set at this

screen. See “Wireless Entry/Exit Remote”

beginning on page 128.

Table 4. Installer Setup (ISU) Table. (Continued)

ISU

Number

Installer Setup

Name

Settings

Default

Residential,

Commercial

or Both

Requires

EIM

Notes

Advertising