THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

43

68-0311—02

4050

Outdoor

Temperature used

with Minimum Heat

Recovery Ramp

Rate

Off
-20° F to 100°F

0° F

Commercial No

Off: The heating system will begin recovery

at the time that is scheduled.

When a Minimum Recovery Ramp Rate is

set, the thermostat will begin recovery

early to ensure the temperature is reached

at the scheduled time.

Set a Minimum Recovery Ramp Rate

based on the rate that the heating system

can recover at for a cold day in your region.

Default setting is 5° F / hour.

If an outdoor sensor is installed, set an

Outdoor Temperature that is representative

of a cold day in your region to be

associated with the Minimum Recovery

Ramp Rate. The thermostat will begin

recovery at the optimal time based on a

calculated ramp rate, allowing the system

to recover on time and save energy during

changing outdoor conditions.

During recovery, the setpoint changes at a

rate in degrees per hour depending on the

outdoor temperature. If there is no outdoor

sensor, the Minimum Recovery Ramp

Rate is used.

4060

Maximum Heat

Recovery Ramp

Rate

Off
1° F/hr to 20° F/hr

8° F/hr

Commercial No

Off: The heating system will begin recovery

at the time that is scheduled.

When a Maximum Recovery Ramp Rate is

set, the thermostat will begin recovery

early to ensure the temperature is reached

at the scheduled time.

Set a Maximum Recovery Ramp Rate

based on the rate that the heating system

can recover at for a mild day in your region.

Default setting is 8° F / hour.

Set an Outdoor Temperature that is

representative of a mild day in your region

to be associated with the Maximum

Recovery Ramp Rate. The thermostat will

begin recovery at the optimal time based

on a calculated ramp rate, allowing the

system to recover on time and save energy

during changing outdoor conditions.

During recovery, the setpoint changes at a

rate in degrees per hour depending on the

outdoor temperature.