Economizer and Time of Day (TOD)

Operation

Economizer

The thermostat controls an economizer module to provide

ventilation during occupied periods and free cooling when

outdoor conditions are favorable. In some climates the cooling

system may run several hours when it may not be required to

maintain indoor comfort. When outdoor conditions are

favorable, ventilation with outdoor air can achieve the same

level of comfort at lower cost. Table 9 explains how the

Economizer Module is controlled by the thermostat.

The thermostat works with the Jade W7212 Economizer

Module for conventional systems and the Jade W7213 and

W7214 Economizer Modules for heat pump systems.

Time of Day (TOD)

The thermostat can be set up for a Time of Day output in the

installer setup. This output is commonly used to control lighting

panels, turning them on for occupied periods and off for

unoccupied periods. Table 10 explains how the TOD feature

works with various thermostat modes.

The Economizer Module and Time of Day output connect to

the A-L/A terminal at the thermostat or EIM and are set up at

ISU 2220.

Fig. 305.

Pre-Occupancy Purge

The thermostat can be set up for Pre-Occupancy Purge in the

installer setup (ISU 4010). When setup for Pre-Occupancy

Purge, the thermostat runs the fan 1 to 3 hours before each

occupied period to provide a comfortable workplace upon

arrival. Options are Off and 1 to 3 hours.

Fig. 306.

Table 9. Economizer Operation.

Thermostat Mode

Equipment Operation

A-L/A terminal:

Economizer

Occupied

Heat/Cool/Fan running

ON

Occupied

temporarily

Heat/Cool/Fan running

Occupied

Heat/Cool/Fan NOT

running

Occupied

temporarily

Heat/Cool/Fan NOT

running

Pre-occupancy

purge

Fan running

Unoccupied

Cooling system running

Unoccupied

temporarily

Cooling system running

Standby

Cooling system running

Unoccupied

Cooling system NOT

running

OFF

Unoccupied

temporarily

Cooling system NOT

running

Standby

Cooling system NOT

running

ON

Non-programmable Fan running
Non-programmable Fan NOT running

OFF

Table 10. TOD Operation.

Thermostat Mode

A-L/A terminal:

TOD

Occupied

ON

Occupied temporarily
Temperature overrides
Unoccupied

OFF

Unoccupied temporarily
Standby
Non-programmable