Wiring guide — Wired Indoor Sensors

Use the S1, S2, S3, or S4 terminals for wired sensors.

CAUTION

Electrical Interference (Noise) Hazard.

Can cause erratic system operation.

Keep wiring at least one foot away from large inductive

loads such as motors, line starters, lighting ballasts and

large power distribution panels.

Use shielded cable to reduce interference when

rerouting is not possible.

IMPORTANT

Erratic temperature readings from a sensor can occur

as a result of any of the wiring practices described

below. Avoid these practices to assure correct opera-

tion. Use shielded cable to reduce interference if

rerouting sensor wiring is not possible.

— Be sure wires have a cable separate from the thermo-

stat cable.

— Do not route temperature sensor wiring with building

power wiring, next to control contactors or near light

dimming circuits, electric motors or welding

equipment.

— Avoid poor wiring connections.

— Avoid intermittent or missing building earth ground.

CAUTION

Electrical Shock Hazard.

Can cause electrical shock or equipment damage.

Disconnect power supply before connecting wiring.

Wiring 4 C7189U1005 sensors (10k ohm) for temperature

averaging network. Select 10K in the Installer Setup (ISU

5030) when using C7189U1005 sensor(s).

Fig. 351. Wiring 4 C7189U sensors.

Wiring 2 TR21 sensors (20k ohm) and 1 TR21-A sensor (10k

ohm) for temperature averaging network. Select 20K in the

Installer Setup (ISU 5030) when using 2 TR21 sensors and 1

TR21-A sensor.

Fig. 352. Wiring 2 TR21 sensors and 1 TR21-A sensor.

Wiring 4 TR21 sensors (20k ohm). Select 20K in the Installer

Setup (ISU 5030) when using TR21 sensor(s).

Fig. 353. Wiring 4 TR21 sensors.

Wiring 2 TR21-A sensors (10k ohm) for temperature averaging

network. Select 20K in the Installer Setup (ISU 5030) when

using 2 TR21-A sensors in series. Note: The TR21-A sensor

must be used in combination with TR21 or TR21-A sensor.

Fig. 354. Wiring 2 TR21-A sensors.

C7189

C7189

C7189

C7189

EIM

M31472

THE NUMBER OF C7189U SENSORS MUST BE

A SQUARE NUMBER (1, 4, 9, 16, ETC.)

1

1

M31473

EIM

TR21-A

T3

T4

TR21

TR21

M31474

EIM

TR21

TR21

TR21

TR21

M31475

EIM

TR21-A

T3

T4

TR21-A

T3

T4