26

2090

What Terminals are

Wired to Cool -

Stage 4?

None
U1
U2
U3

Default varies

based on

previous

selections

Commercial No

Cool Stage 4 is only available if ISU 1010 is

Commercial.

Cool Stage 4 must be wired to a universal

terminal (U1, U2 or U3).

U1, U2 and U3 are normally open dry

contacts when configured for a stage of

Cool. U1, U2 and U3 require power from a

system transformer or a separate

transformer.

U3 is only available on the Equipment

Interface Module (EIM).

2100

What Terminals are

Wired to Heat -

Stage 3?

None
U1
U2
U3

Default varies

based on

previous

selections

Both

No

THX9321 Thermostat Only:

This ISU is only displayed on the THX9321

thermostat when it is wired directly to the

equipment (Equipment Interface Module is

NOT used).

Heat Stage 3 must be wired to a universal

terminal (U1 or U2).

U1 and U2 are normally open dry contacts

when configured for a stage of Heat. U1

and U2 require power from a system

transformer or a separate transformer.

2110

Fan Operation in

Heat

No Fan
Equipment Controls Fan
Thermostat Controls Fan

Thermostat

Controls Fan

Both

No

This ISU is only displayed when ISU 2010

Heating Equipment Type is Electric Forced

Air, Hot Water Fan Coil or Other.

The thermostat automatically defaults to

Equipment Controls Fan when ISU 2010

Heating Equipment Type is Standard

Efficiency Gas Forced Air, High Efficiency

Gas Forced Air or Oil Forced Air.

No Fan is only displayed when ISU 2010

Heating Equipment Type is Other.

2120

Backup Heat Type

None
Standard Efficiency Gas Forced Air
High Efficiency Gas Forced Air
Oil Forced Air
Electric Forced Air
Hot Water Fan Coil
Hot Water Radiant Heat
Other

None

Both

No

This ISU is only displayed when ISU 2010

Heating Equipment Type is Hot Water

Radiant Heat, Steam, Hot Water Fan Coil,

Electric Forced Air or Other.

The list of Backup Heat Types will vary

based on the type of primary heat selected

at ISU 2010 Heating Equipment Type.

When ISU 2010 Heating Equipment Type is

Hot Water Radiant Heat, the thermostat

keeps the Hot Water Radiant Heat on when

it calls for Backup Heat.

When ISU 2010 Heating Equipment Type is

Steam, the thermostat keeps the Steam

Heat on when it calls for Backup Heat.

When ISU 2010 Heating Equipment Type is

Hot Water Fan Coil, Electric Forced Air or

Other, you can select how the backup

operates. See ISU 2150 Backup Heat

Operation.

Table 4. Installer Setup (ISU) Table. (Continued)

ISU

Number

Installer Setup

Name

Settings

Default

Residential,

Commercial

or Both

Requires

EIM

Notes