Set up ventilation – Honeywell PRESTIGE THX9321 User Manual

Page 113

Advertising
background image

THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

113

68-0311—02

Ventilation Fan Control (ISU 10060)

Thermostat Controls Fan

The thermostat turns on the ventilator and the fan when

ventilation is needed.

Equipment Controls Fan

The thermostat turns on the ventilator when ventilation is

needed. The fan is controlled by the equipment.

Ventilation Priority (ISU 10125)

Lockouts are Priority

The thermostat places a priority on lockouts versus the

ASHRAE 62.2 ventilation standard. The thermostat will not

run ventilation during the following lockout conditions (if

configured) unless you manually call for ventilation:

— Lockout Ventilation during Outdoor Conditions (ISU

10130)

— Lockout Ventilation on Humidification or Dehumidifica-

tion Calls (ISU 10140)

— Lockout Ventilation during “Sleep” (Residential) or

“Unoccupied” (Commercial) program periods. Note:

This option is set by the user on the Ventilation screen

in the Menu.

ASHRAE is Priority

ASHRAE requires additional ventilation following a long off

cycle. The thermostat meets the ASHRAE 62.2 ventilation

standard by running additional ventilation when outdoor

conditions are favorable. If ASHRAE cannot be met when

outdoor conditions are favorable, the thermostat will

override the outdoor lockouts and run ventilation. When

using this option, it is recommended to increase the rate

(CFM) of the ventilation equipment to meet the ASHRAE

62.2 ventilation standard in a shorter run time.

NOTES: ISU 10140 “Lockout Ventilation on Humidification or

Dehumidification Calls” is not an option when you

select “ASHRAE is Priority”.

The ability to lockout ventilation during the “Sleep” or

“Unoccupied” program periods is not an option when

you select “ASHRAE is Priority”.

Ventilation — Outdoor Condition Lockouts

(ISU 10130)

Ventilation will not operate when outdoor conditions exceed the

lockout settings unless you manually call for ventilation or

Ventilation Priority (ISU 10125) is set to

ASHRAE is Priority

and ventilation is needed to meet ASHRAE. Lockouts can

prevent ventilation during extreme weather conditions to keep

humid, hot, and cold air out of the home.

NOTE: This feature requires an outdoor sensor.

If the outdoor sensor also measures humidity, ventilation will

not be allowed when the outdoor dewpoint is above the level

you set. Options are:

• Ventilation Low Temperature Lockout Setpoint

(Off, -20° to 40° F)

• Ventilation High Temperature Lockout Setpoint

(Off, 80° to 110° F)

• Ventilation High Dewpoint Lockout Setpoint

(Off, 65° to 85° F)

Refer to the information below if you need assistance setting

the High Dewpoint Lockout.

• Higher than 80: Extremely uncomfortable

• 75 to 80: Very uncomfortable

• 70 to 74: Quite uncomfortable

• 65 to 69: Somewhat uncomfortable

Ventilate on High Indoor Humidity (ISU

10160)

If set to ventilate on high indoor humidity, the ventilator turns on

to remove excess humidity if the indoor humidity is 10% above

the Humidification setting. The thermostat must be in the heat

mode to ventilate on high indoor humidity.

Set up Ventilation

Some screens shown in this section may not appear on the

thermostat, depending on how you set up ventilation.

1. Select the Ventilation Type in ISU 10000. See Fig. 248.

Fig. 248.

2. Select the terminals wired to the Ventilator (or Fresh Air

Damper). See Fig. 249.

Fig. 249.

3. Select the Ventilation Control Method. See “Ventilation

Control Methods (ISU 10050)” on page 112 for more

information. See Fig. 250.

Fig. 250.

Advertising
This manual is related to the following products: