Honeywell PRESTIGE THX9321 User Manual

Page 33

Advertising
background image

THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

33

68-0311—02

3050

Staging Control -

Heat Differential

Stage 3

Note: Depending

on the application,

the text displayed

on the screen may

show the specific

heating equipment

type

Comfort
1.0° F to 4.0° F from setpoint (in

0.5° F increments)

Comfort

Both

No

ISU 3010 Temperature Control Options

must be set to Advanced to view or adjust

this ISU.

This ISU is only displayed for conventional

systems that have 3 heat stages.

The indoor temperature must drop to the

selected differential setting before the

thermostat will turn on the stage of

heating. For example, if stage 3 is set to 2°

F (1.0° C), the indoor temperature must be

2° F (1.0° C) away from the setpoint before

stage 3 turns on. When set to Comfort, the

thermostat will use the stage of heating as

needed to keep the indoor temperature

within 1° F (0.5° C) degree of the setpoint.

3060

Staging Control -

Compressor Heat

Differential Stage 1

Comfort
1.0° F to 4.0° F from setpoint (in

0.5° F increments)

Comfort

Both

No

ISU 3010 Temperature Control Options

must be set to Advanced to view or adjust

this ISU.

This ISU is only displayed if ISU 2010

Heating Equipment Type is Geothermal

Radiant Heat and ISU 2050 Geothermal

Forced Air System is set to Used for

Heating and Cooling.

The indoor temperature must drop to the

selected differential setting before the

thermostat will turn on the stage of

heating. For example, if stage 1 is set to 2°

F (1.0° C), the indoor temperature must be

2° F (1.0° C) away from the setpoint before

stage 1 turns on. When set to Comfort, the

thermostat will use the stage of heating as

needed to keep the indoor temperature

within 1° F (0.5° C) degree of the setpoint.

3060

Staging Control -

Compressor Heat

Differential Stage 2

Comfort
1.0° F to 4.5° F from setpoint (in

0.5° F increments)

Comfort

Both

No

ISU 3010 Temperature Control Options

must be set to Advanced to view or adjust

this ISU.

This ISU is only displayed if ISU 2010

Heating Equipment Type is Air to Air Heat

Pump, Geothermal Heat Pump or

Geothermal Radiant Heat and there are 2

compressor stages.

The indoor temperature must drop to the

selected differential setting before the

thermostat will turn on the stage of

heating. For example, if stage 2 is set to 2°

F (1.0° C), the indoor temperature must be

2° F (1.0° C) away from the setpoint before

stage 2 turns on. When set to Comfort, the

thermostat will use the stage of heating as

needed to keep the indoor temperature

within 1° F (0.5° C) degree of the setpoint.

Table 4. Installer Setup (ISU) Table. (Continued)

ISU

Number

Installer Setup

Name

Settings

Default

Residential,

Commercial

or Both

Requires

EIM

Notes