Honeywell PRESTIGE THX9321 User Manual

Page 53

Advertising
background image

THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

53

68-0311—02

6160

Fan Failure Alert

Dry Contact Setup

Normally Open when Fan is

Running
Normally Closed when Fan is

Running

Normally

Closed when

Fan is Running

Both

Yes

Dry Contact Alerts require an EIM

(Equipment Interface Module).

Choose an option appropriate for the type

of device installed:

Normally Open when Fan is Running: The

Dry Contact device is open when the fan is

running and will close when the fan is not

running.

Normally Closed when Fan is Running: The

Dry Contact device is closed when the fan

is running and will open when the fan is not

running.

6170

What Terminals are

Wired to the

Custom Alert Dry

Contact?

None
S1
S2
S3
S4

None

Both

Yes

Dry Contact Alerts require an EIM

(Equipment Interface Module).

6180

Custom Alert Dry

Contact Setup

Normally Open
Normally Closed

Normally Open Both

Yes

Dry Contact Alerts require an EIM

(Equipment Interface Module).

Choose an option appropriate for the type

of device installed:

Normally Open: The Dry Contact device is

normally open and will close when the

device is activated.

Normally Closed: The Dry Contact device is

normally closed and will open when the

device is activated.

6190

Custom Alert Name

View/Edit Custom Alert

View/Edit

Custom Alert

Both

Yes

Dry Contact Alerts require an EIM

(Equipment Interface Module).

Enter a name for the custom alert dry

contact. The thermostat displays this name

including a brief message (entered on the

next screen - ISU 6200) when a dry contact

device detects a problem.

6200

Custom Alert

Message

View/Edit Custom Alert

View/Edit

Custom Alert

Both

Yes

Dry Contact Alerts require an EIM

(Equipment Interface Module).

Enter a message for the custom alert dry

contact. The thermostat displays this

message when a dry contact device detects

a problem.

7000

Filter Type

None
Electronic Air Cleaner
Media

Media

Both

No

7020

Number of Air

Filters

1 to 2

1

Both

No

Table 4. Installer Setup (ISU) Table. (Continued)

ISU

Number

Installer Setup

Name

Settings

Default

Residential,

Commercial

or Both

Requires

EIM

Notes