THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

68-0311—02

40

3160

Backup Heat Cycles

Per Hour - Stage 2

1 to 12 CPH

Default varies

based on

heating

equipment type

selected

Both

No

ISU 3010 Temperature Control Options

must be set to Advanced to view or adjust

cycle rate.

This ISU is only displayed when ISU 2070

or 2130 Backup Heat Stages is set to 2

stages.

Cycle rate limits the maximum number of

times the system can cycle in a 1 hour

period measured at a 50% load. For

example, when set to 3 CPH, at a 50% load,

the most the system will cycle is 3 times

per hour (10 minutes on, 10 minutes off).

The system cycles less often when load

conditions are less than or greater than a

50% load. The thermostat automatically

defaults to the recommended cycle rate

based on the heating equipment type that is

used. You can change the cycle rate as

needed. Default for commonly used

systems are shown below.

Standard Efficiency Gas Forced Air = 5 CPH

High Efficiency Gas Forced Air = 3 CPH

Oil Forced Air = 5 CPH

Electric Forced Air = 9 CPH

Hot Water Fan Coil = 3 CPH

Hot Water Radiant Heat = 3 CPH

Geothermal Radiant Heat = 3 CPH

Steam = 1 CPH

Gravity = 1 CPH

3170

Cooling Throttling

Range

1° F to 30° F

2° F

Commercial No

The default Cooling Throttling range is 2° F

(1.5° C) which is appropriate for most

applications. Do not change this setting

unless advised to do so by Honeywell

technical support.

The throttling range controls the cycling of

the system and helps to compensate for

load changes, equipment sizing and

thermostat mounting location.

3180

Cooling Integral

0, 100 to 25,000 sec

10,000 sec

Commercial No

The default Cooling Integral is 10,000

seconds which is appropriate for most

applications. Do not change this setting

unless advised to do so by Honeywell

technical support.

The integral controls how much droop is

used.

3190

Cooling Derivative

0, 100 to 25,000 sec

0 sec

Commercial No

The default Cooling Derivative is 0 seconds

which is appropriate for most applications.

Do not change this setting unless advised

to do so by Honeywell technical support.

The derivative makes adjustments to the

algorithm for fast acting systems.

Table 4. Installer Setup (ISU) Table. (Continued)

ISU

Number

Installer Setup

Name

Settings

Default

Residential,

Commercial

or Both

Requires

EIM

Notes