THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

61

68-0311—02

10120 Ventilation Percent

On Time

10% to 100% (in 10%

increments)

30%

Both

No

The thermostat operates ventilation

equipment based on a percentage entered

in the installer setup (ISU 10120). For

example, if Percent on Time is set to 50%,

the ventilation equipment will run at

random times during a 1 hour period until

it reaches a 50% run time (approximately

30 minutes).

10125 Ventilation Priority

Lockouts are Priority
ASHRAE is Priority

Lockouts are

Priority

Residential

No

Lockouts are Priority: The thermostat

places a priority on lockouts versus the

ASHRAE 62.2 ventilation standard. The

thermostat will not run ventilation during

the following lockout conditions (if

configured) unless you manually call for

ventilation:

Lockout Ventilation during Outdoor

Conditions (ISU 10130)

Lockout Ventilation on Humidification or

Dehumidification Calls (ISU 10140)

Lockout Ventilation during “Sleep”

(Residential) or “Unoccupied” (Commercial)

program periods. Note: This option is set by

the user on the Ventilation screen in the

Menu.

ASHRAE is Priority: ASHRAE requires

additional ventilation following a long off

cycle. The thermostat meets the ASHRAE

62.2 ventilation standard by running

additional ventilation when outdoor

conditions are favorable. If ASHRAE cannot

be met when outdoor conditions are

favorable, the thermostat will override the

outdoor lockouts and run ventilation. When

using this option, it is recommended to

increase the rate (CFM) of the ventilation

equipment to meet the ASHRAE 62.2

ventilation standard in a shorter run time.

Notes:

ISU 10140 “Lockout Ventilation on

Humidification or Dehumidification Calls” is

not an option when you select “ASHRAE is

Priority”.

The ability to lockout ventilation during the

“Sleep” or “Unoccupied” program periods is

not an option when you select “ASHRAE is

Priority”.

10130 Ventilation Low

Temperature

Lockout

Off
-20° F to 40° F (in 5° F

increments)

Off

Both

No

Requires an outdoor sensor.

This ISU is only displayed when ISU 10000

Ventilation Type is set to ERV / HRV or

Fresh Air Damper.

See “Ventilation — Outdoor Condition

Lockouts (ISU 10130)” beginning on

page 113.

Table 4. Installer Setup (ISU) Table. (Continued)

ISU

Number

Installer Setup

Name

Settings

Default

Residential,

Commercial

or Both

Requires

EIM

Notes