If you decide to set up diagnostics later, Run a test for each stage – Honeywell PRESTIGE THX9321 User Manual

Page 89

Advertising
background image

THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

89

68-0311—02

5. For Air-to-Air Heat Pumps, press the up/down arrows to

set the maximum time duration of a defrost cycle. Default

is 10 minutes. Delta T is not monitored during a defrost

cycle. Check the heat pump documentation for the

defrost cycle time.

Fig. 153.

6. When you have completed Installer Setup (see “Installer

Options” beginning on page 21), you will be asked to fin-

ish setting up Diagnostics.

Fig. 154.

7. If you press Set Up Diagnostics, you will enter the

Equipment Test. See “Run a Test for Each Stage”

beginning on page 89.

8. If you press I’ll do it later, you will be reminded to finish

setting up diagnostics the next time you exit installer

setup. You can also finish setting up diagnostics by

following the procedure in “If You Decide to Set Up

Diagnostics Later”.

After Delta T Diagnostics Setup is complete, the thermostat will

detect typical failures such as no heating or no cooling and

performance related issues that are typically caused by a dirty

air filter, blocked registers, loss of refrigerant, dirty a-coil,

frozen a-coil, cracked heat exchanger, dirty burners, etc.

If You Decide to Set Up Diagnostics Later

When you are ready to set up diagnostics, follow these steps:

1. From the Home screen, press MENU.

2. Scroll down and press Installer Options.

3. Enter the passcode and press Done (see Note).

NOTE: The passcode is the date code printed on the

back of the thermostat or press

MENU > EQUIPMENT STATUS to find the date

code.

4. Press Set Up Diagnostics.

Fig. 155.

5. Proceed to “Run a Test for Each Stage”.

Run a Test for Each Stage

Follow these steps to run a test for each stage in the HVAC

system.

1. Turn on stage 1.

Fig. 156.

2. For each stage you test, wait until Delta T begins to sta-

bilize, then turn on the next stage (if present). See Fig.

157 for an example.

Fig. 157.

3. Press Next Step after Delta T stabilizes for the last stage.

The thermostat saves the Delta T and Run Time Data for

each stage you test and is displayed on the next screen.

NOTE: The thermostat only saves test data for stages

that run 1 minute or longer.