THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

68-0311—02

66

13130 Allow Cool Delta T

Diagnostics when

Indoor

Temperature is

[Indoor

Temperature

Range]

Minimum Setting

No Limit
35° F to 115° F (in 5° F

increments)

No Limit

(Always)

Both

Yes

This ISU only applies to Cooling.

This ISU is only displayed when ISU 13015

Set Advanced Diagnostic Options is set to

Yes.

The thermostat monitors Delta T of the

system ONLY when the indoor temperature

is within a certain range. Set to No Limit to

monitor Delta T during all indoor

temperature conditions.

13130

Maximum Setting

No Limit
40° F to 120° F (in 5° F

increments)

No Limit

(Always)

Both

Yes

13140 Allow Cool Delta T

Diagnostics when

Indoor Humidity is

[Indoor Humidity

Range]

Minimum Setting

No Limit
0% to 95% (in 5% increments)

No Limit

(Always)

Both

Yes

This ISU only applies to Cooling.

This ISU is only displayed when ISU 13015

Set Advanced Diagnostic Options is set to

Yes.

The thermostat monitors Delta T of the

system ONLY when the indoor humidity is

within a certain range. Set to No Limit to

monitor Delta T during all indoor humidity

conditions.

13140

Maximum Setting

No Limit
5% to 100% (in 5% increments)

No Limit

(Always)

Both

Yes

13150 Allow Cool Delta T

Diagnostics when

Outdoor

Temperature is

[Outdoor

Temperature

Range]

Minimum Setting

No Limit
-50° F to 135° F (in 5° F

increments)

No Limit

(Always)

Both

Yes

This ISU only applies to Cooling.

This ISU is only displayed when ISU 13015

Set Advanced Diagnostic Options is set to

Yes.

The thermostat monitors Delta T of the

system ONLY when the outdoor

temperature is within a certain range. Set

to No Limit to monitor Delta T during all

outdoor temperature conditions.

13150

Maximum Setting

No Limit
-45° F to 140° F (in 5° F

increments)

No Limit

(Always)

Both

Yes

13160 Allow Cool Delta T

Diagnostics when

Outdoor Humidity

is [Outdoor

Humidity Range]

Minimum Setting

No Limit
0% to 95% (in 5% increments)

No Limit

(Always)

Both

Yes

This ISU only applies to Cooling.

This ISU is only displayed when ISU 13015

Set Advanced Diagnostic Options is set to

Yes.

The thermostat monitors Delta T of the

system ONLY when the outdoor humidity is

within a certain range. Set to No Limit to

monitor Delta T during all outdoor humidity

conditions.

13160

Maximum Setting

No Limit
5% to 100% (in 5% increments)

No Limit

(Always)

Both

Yes

Table 4. Installer Setup (ISU) Table. (Continued)

ISU

Number

Installer Setup

Name

Settings

Default

Residential,

Commercial

or Both

Requires

EIM

Notes