Set up the dry contact alerts, Warning, Full drain pan alert – Honeywell PRESTIGE THX9321 User Manual

Page 96: Dirty filter alert, Water leak alert, System shutdown alert, Service needed alert, Fan failure alert, Custom alert

Advertising
background image

THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

68-0311—02

96

When the user presses the alert for more info, the Notification

screen is displayed, prompting them to contact their dealer.

See Fig. 185 as an example.

Fig. 185.

The following dry contact alerts are available.

Full Drain Pan Alert

When the dry contact device detects that the condensate drain

pan is full, the thermostat provides an alert to the user.

NOTE: If you want the compressor to turn off when the

drain pan is full, wire the system so the dry con-

tact device turns off the compressor when the

drain pan is full.

Dirty Filter Alert

When the dry contact device detects a dirty air filter (pressure

drop across the filter), the thermostat provides an alert to the

user to replace the filter.

Water Leak Alert

When the dry contact device detects a water leak, the

thermostat provides an alert to the user.

System Shutdown Alert

When the dry contact device detects a critical problem with the

system, the thermostat provides an alert to the user indicating

that the system was shut down.

When the dry contact device detects a problem with the

system (for example, smoke detection), the thermostat will not

call for heating, cooling, fan or IAQ equipment until the dry

contact is deactivated or the feature is unconfigured at the

thermostat.

Service Needed Alert

When the dry contact device detects an issue that requires

service, the thermostat provides an alert to the user.

Fan Failure Alert

The Fan Failure Alert protects the equipment when there is no

airflow. When the dry contact device (for example, sail switch)

detects no air flow for 5 minutes after a call for forced air heat,

cool, or fan, the thermostat provides an alert to the user

indicating that the system was shut down due to a lack of

airflow.

The thermostat will call for the fan and lockout all other

equipment until the dry contact device senses air flow again or

the feature is unconfigured at the thermostat.

Custom Alert

Allows the dealer to enter a custom alert to be displayed when

a dry contact device is activated. For example, a float switch

can detect when your sump pump is not working.

Set Up the Dry Contact Alerts

WARNING

Equipment Damage Hazard.

Do not apply power to S1, S2, S3, or S4 terminals. Do

not connect a temperature sensor to the S1, S2, S3, or

S4 terminals if setup for a dry contact device.

IMPORTANT

The dry contact device must be rated for low voltage.

NOTE: You can connect multiple Dry Contact devices in

parallel to the S1, S2, S3, or S4 terminals.

You can connect the S1, S2, S3, or S4 terminals on the EIM to

a dry contact device to display an alert. Dry contact alerts

include Full Drain Pan, Dirty Filter, Water Leak, System

Shutdown, Service Needed, Fan Failure and Custom Alert. A

dry contact device can be normally open (shown in diagram) or

normally closed.

Fig. 186. Wiring dry contact devices.

MULTIPLE DRY CONTACT DEVICES

ON ONE SET OF TERMINALS

EIM

ONE DRY CONTACT DEVICE

MULTIPLE DRY CONTACT DEVICES

ON ONE SET OF TERMINALS

EIM

ONE DRY CONTACT DEVICE

S4

S4

S3

S3