Thx9321 prestige, Iaq with eim – Honeywell PRESTIGE THX9321 User Manual

Page 148

Advertising
background image

THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

68-0311—02

148

Fig. 338. Wood stove with heat pump and backup electric strips. (For applications in which the thermostat only needs to

run the blower fan when stove is hot).

1 Select Geothermal Radiant Heat at ISU 2010. Connect Fan to U1, U2, or U3 as shown in the wiring diagram.
2 “U” terminals are normally open dry contacts when set up for geothermal radiant heat.
3 L/A terminal sends continuous output when thermostat is set to EM HEAT mode except when set up for Economizer or TOD.

See “Economizer Module Wiring Diagrams” beginning on page 151.

4 Y2 used with heat pumps that have 2 compressor stages.

NOTE: In Fig. 338, the thermostat will energize only the fan with a call for stage 1 heat. If the wood stove is hot, heat

comes from the fan coil. If the wood stove is cold, only the fan runs. The thermostat will upstage to the heat

pump and backup heat as needed to maintain the temperature.

O/B

AUX1

AUX2

O

W

Y

Y2

G

R

C

O

Y

Y2

R

C

L/A

TO THERMOSTAT

THERMOSTAT/EIM

HEAT PUMP

AIR HANDLER

HEAT PUMP

M31487

2

4

4

1