Honeywell PRESTIGE THX9321 User Manual

Page 62

Advertising
background image

THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

68-0311—02

62

10130 Ventilation High

Temperature

Lockout

Off
80° F to 110° F (in 5° F

increments)

Off

Both

No

Requires an outdoor sensor.

This ISU is only displayed when ISU 10000

Ventilation Type is set to ERV / HRV or

Fresh Air Damper.

See “Ventilation — Outdoor Condition

Lockouts (ISU 10130)” beginning on

page 113.

10130 Ventilation High

Dew Point Lockout

Off
65° F to 85° F (in 5° F increments)

Off

Both

No

Requires a Wireless Outdoor Sensor

(sense outdoor humidity).

This ISU is only displayed when ISU 10000

Ventilation Type is set to ERV / HRV or

Fresh Air Damper.

See “Ventilation — Outdoor Condition

Lockouts (ISU 10130)” beginning on

page 113.

10140 Lockout Ventilation

on Humidification

or

Dehumidification

Calls

Off
On

Off

Both

No

This feature is used to help reach the user's

desired humidity level by not allowing the

ventilation equipment to run during a call

for humidification or dehumidification.

Off: Ventilation is allowed to run during a

call for humidification or dehumidification.

On: Ventilation is NOT allowed to run

during a call for humidification or

dehumidification.

10160 Ventilate on High

Indoor Humidity

Off
On (Heat Mode Only)

On (Heat Mode

Only)

Both

No

This ISU is only displayed when ISU 10000

Ventilation Type is set to ERV / HRV.

Off: The humidity level has no effect on

ventilation.

On: The thermostat removes excess

humidity by turning on the ventilator when

the indoor humidity rises 10% above the

user's humidification setting. The

thermostat must be in the heat mode to

ventilate on high humidity.

10170 Ventilator Core

Cleaning Reminder

Off
3, 6, 9, 12 Calendar Months

Off

Both

No

10170 Ventilator Filter

Cleaning Reminder

Off
3, 6, 9, 12 Calendar Months

Off

Both

No

11000 Number of UV

Devices

0, 1, 2

0

Both

No

Press the up/down arrows to select the

number of UV devices installed in the

system. Some systems may have two UV

devices, one for the A-Coil and another for

Air Treatment. A replacement reminder can

be setup for each one. Select 0 if no UV

devices are installed.

11050 UV Bulb 1

Replacement

Reminder

Note: “1” is not

displayed if there is

only 1 UV Bulb

Off, 6, 12, 24 Calendar Months

Off

Both

No

Table 4. Installer Setup (ISU) Table. (Continued)

ISU

Number

Installer Setup

Name

Settings

Default

Residential,

Commercial

or Both

Requires

EIM

Notes