Honeywell PRESTIGE THX9321 User Manual

Page 60

Advertising
background image

THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

68-0311—02

60

10000 Ventilation Type

None
ERV / HRV
Passive (Fan Only)
Fresh Air Damper

None

Both

No

None: The thermostat does not control

ventilation.

ERV/HRV: The thermostat controls an

Energy Recovery Ventilator or Heat

Recovery Ventilator for ventilation.

Passive (Fan Only): The thermostat turns

on the fan for ventilation.

Fresh Air Damper: The thermostat turns on

the fan and opens a fresh air damper for

ventilation.

10020 What Terminals are

Wired to the

Ventilator?

What Terminals are

Wired to the Fresh

Air Damper?

Note: Installer

Setup Name varies

depending on the

ventilation

equipment

installed.

None
U1
U2
U3

Thermostat

defaults to the

next unused

universal

terminal (U1,

U2, U3).

Both

No

Number of Universal Outputs:

THX9321 Thermostat: U1 and U2 terminals

Equipment Interface Module (EIM): U1, U2

and U3 terminals

U1, U2, U3 are dry contacts that require

power. See “Wiring IAQ Equipment or a

Heat/Cool Stage to the Universal

Terminals” beginning on page 149.

10050 Ventilation Control

Method

ASHRAE
Percent On Time

Defaults to

ASHRAE

when ISU 1010

Application is

set to

Residential.

Percent on

Time is the

only choice

when ISU 1010

Application is

set to

Commercial.

Both

No

See “Ventilation Control Methods (ISU

10050)” beginning on page 112.

10060 Ventilation Fan

Control

Thermostat Controls Fan
Equipment Controls Fan

Thermostat

Controls Fan

Both

No

Thermostat Controls Fan: The thermostat

turns on the ventilation equipment and the

fan when ventilation is needed.

Equipment Controls Fan: The thermostat

turns on the ventilation equipment when

ventilation is needed. The fan is controlled

by the equipment.

10090 Number of

Bedrooms

1 to 6

2 bedrooms

Residential

No

This ISU is only displayed when ISU10050

Ventilation Control Method is set to

ASHRAE (Residential only).

10090 Size of House

1000 to 5000 sq. ft. (in 100 sq. ft.

increments)

(90 to 460 sq. m.)

1000 sq. feet

Residential

No

This ISU is only displayed when ISU10050

Ventilation Control Method is set to

ASHRAE (Residential only).

10100 Enter Equipment

Ventilation Rate

30 to 350 CFM (in 5 CFM

increments)

(850 - 9900 LPM)

150

Residential

No

This ISU is only displayed when ISU10050

Ventilation Control Method is set to

ASHRAE (Residential only).

Table 4. Installer Setup (ISU) Table. (Continued)

ISU

Number

Installer Setup

Name

Settings

Default

Residential,

Commercial

or Both

Requires

EIM

Notes