Dehumidification - commercial, Dehumidification using the cooling system, Set up dehumidification with cooling system – Honeywell PRESTIGE THX9321 User Manual

Page 109

Advertising
background image

THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

109

68-0311—02

Dehumidification - Commercial

The thermostat reads the indoor humidity level and allows the

user to set a dehumidification setting. The thermostat controls

the humidity level using the cooling system or a dehumidifier.

If humidification and dehumidification are setup to operate in

the same system mode (Heat, Cool, Off) and you are sensing

humidity from one location, the thermostat will automatically

enforce a 15% deadband between the humidification and

dehumidification settings. The thermostat will automatically

switch between humidification and dehumidification to maintain

the desired humidity level.

If humidification and dehumidification are setup to operate in

the same system mode (Heat, Cool, Off) and you are sensing

humidity from two different locations using a remote wireless

indoor sensor (for example, main level and crawl space), the

thermostat will allow humidification and dehumidification to

operate at the same time, and there is no deadband between

humidification and dehumidification settings.

Dehumidification Equipment Options: (ISU 9000)

• A/C with Low Speed Fan

• A/C with High Speed Fan

• Hot Gas Bypass

• Dehumidifier

NOTE: Hot Gas Bypass - During a call for dehumidifica-

tion, the cooling capacity will be used to remove

more latent heat than sensible heat. The operation

of Hot Gas Bypass varies by equipment. For more

details, contact the equipment manufacturer.

Dehumidification using the Cooling System

Dehumidification using A/C with Low Speed Fan, A/C with High

Speed Fan or Hot Gas Bypass, has the following methods of

dehumidification control (ISU 9080):

Fig. 234.

Basic: This option uses the cooling system to reach the

desired humidity level. Minimum On Time, High Humidity

Comfort Reset and Reheat are not used with this method. This

setting is commonly used if your dehumidification equipment is

Hot Gas Bypass.

Minimum On Time (ISU 9090): This option ensures that the

compressor runs long enough to effectively reduce humidity

when the cooling equipment is cycled on. The compressor will

run for the minimum “on time” you set until the desired humidity

level is reached.

High Humidity Comfort Reset (ISU 9100): This option uses

the cooling system to lower the temperature up to 5° F below

the current cool setpoint until the desired humidity is reached.

The high humidity comfort range is from 1° to 5° F.

High Humidity Comfort Reset with Minimum On Time (ISU

9090 and 9100): This method uses both options above to

reduce humidity while maintaining a comfortable temperature.

Reheat (ISU 9080): This option allows heating to run during

dehumidification to help maintain a comfortable temperature. If

only cooling stage 1 is used, during the “off” cycle, both cooling

and heating run at the same time as needed to dehumidify

without overcooling. This option cannot be used in the Heat

mode. This option is effective only if using a system with the A-

Coil located before the heating coil (heat exchanger). This

feature requires a conventional forced air heating system (gas,

oil, or electric) in the application.

NOTE: Reheat can be used on heat pump applications

that have a forced air backup heat source (gas,

oil, or electric). The thermostat will turn on the

first stage of forced air backup heat during

Reheat.

NOTE: Reheat can be used on systems where the A-Coil

is located after the heating coil (heat exchanger),

but it is not effective at removing humidity.

Reheat with Minimum On Time (ISU 9080 and 9090): This

method uses both Reheat and Minimum On Time options

above to reach the desired humidity level.

If set for A/C with Low Speed Fan, configure U1, U2, or U3 as

normally open or normally closed (ISU 9050) and wire to the

Low Speed Fan terminal on the equipment. For example, if the

U1, U2, or U3 terminal is normally closed, it will open when the

thermostat calls for dehumidification.See “Wiring IAQ

Equipment or a Heat/Cool Stage to the Universal Terminals”

beginning on page 149.

NOTE: The thermostat will not lower the fan speed when

the second stage of cooling is on.

Set up Dehumidification With Cooling

System

Some screens shown in this section may not appear on the

thermostat, depending on how you set up dehumidification.

1. Select the Dehumidification Equipment in ISU 9000. See

Fig. 235.

Fig. 235.

Advertising
This manual is related to the following products: