THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

57

68-0311—02

9040

What Terminals are

Wired to A/C with

Low Speed Fan?

What Terminals are

Wired to Hot Gas

Bypass?

What Terminals are

Wired to the

Dehumidifier?

What Terminals are

Wired to the Whole

House

Dehumidifier?

Note: Installer

Setup Name varies

depending on the

dehumidification

equipment

installed.

None
U1
U2
U3

Thermostat

defaults to the

next unused

universal

terminal (U1,

U2, U3).

Both

No

Number of Universal Outputs:

THX9321 Thermostat: U1 and U2 terminals

Equipment Interface Module (EIM): U1, U2

and U3 terminals

U1, U2, U3 are dry contacts that require

power. See “Wiring IAQ Equipment or a

Heat/Cool Stage to the Universal

Terminals” beginning on page 149.

9050

A/C with Low

Speed Fan Setup

Hot Gas Bypass

Setup

Note: Installer

Setup Name varies

depending on the

dehumidification

equipment

installed.

Normally Closed
Normally Open

Defaults to

Normally

Closed when

ISU 9000

Dehumidificati

on Equipment

is A/C with Low

Speed Fan

Defaults to

Normally Open

when ISU 9000

Dehumidificati

on Equipment

is Hot Gas

Bypass

Both

No

Choose an option appropriate for the type

of equipment installed.

Normally Open: U1, U2 or U3 will normally

be open and will close when the thermostat

calls for dehumidification.

Normally Closed: U1, U2 or U3 will

normally be closed and will open when the

thermostat calls for dehumidification.

Number of Universal Outputs:

THX9321 Thermostat: U1 and U2 terminals

Equipment Interface Module (EIM): U1, U2

and U3 terminals

9070

Dehumidification -

Overcooling Limit

0°, 1°, 2°, 3° F

3° F

Residential

No

This ISU is only displayed when ISU 9000

Dehumidification Equipment is set to A/C

with Low Speed Fan or A/C with High

Speed Fan.

The thermostat uses the cooling system to

reduce humidity by lowering the

temperature up to 3° F below the current

cool setpoint until the desired humidity

level is reached.

The thermostat keeps the temperature

below the cooling setpoint until the desired

humidity level is reached.

0° F is only an option when ISU 9000

Dehumidification Equipment is set to A/C

with Low Speed Fan.

Table 4. Installer Setup (ISU) Table. (Continued)

ISU

Number

Installer Setup

Name

Settings

Default

Residential,

Commercial

or Both

Requires

EIM

Notes