Honeywell PRESTIGE THX9321 User Manual

Page 125

Advertising
background image

THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

125

68-0311—02

2. Select the terminals wired to the Remote Setback Dry

Contact device (occupancy sensor) and press Next.

Fig. 301.

3. Select Normally Open when Occupied or Normally

Closed when Occupied based on the type of dry contact

device installed.

NOTE: Normally Open when Occupied: The Dry Con-

tact device is open when the room is occupied

and will close when the room is unoccupied.

Normally Closed when Occupied: The Dry Con-

tact device is closed when the room is occupied

and will open when the room is unoccupied.

Fig. 302.

4. Select a Remote Setback Time Delay. The Remote Set-

back Time Delay forces the thermostat to wait before it

switches from occupied settings to the standby settings.

When set to 0 minutes, the thermostat will switch from

occupied settings to the standby settings immediately

when the room is unoccupied.

Fig. 303.

5. Select the Standby settings that you would like to main-

tain when the occupancy sensor detects the room is

unoccupied.

Fig. 304.