Cool differential, Backup heat differential (droop) – Honeywell PRESTIGE THX9321 User Manual

Page 98

Advertising
background image

THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

68-0311—02

98

Cool Differential

The indoor temperature must rise to the selected differential

setting before the thermostat turns on the stage of cooling. For

example, if stage 2 is set to 2 °F (1.0 °C), the indoor

temperature must be 2 °F (1.0 °C) away from the setpoint

before stage 2 turns on. When set to Comfort, the thermostat

uses the stage cooling as needed to keep the indoor

temperature within 1 °F (0.5 °C) degree of the setpoint. The

thermostat turns on stage 2 (or the next stage) when the

capacity on stage 1 reaches 90%.

TO CHANGE DIFFERENTIAL SETTINGS

1. Select Advanced Options to view/adjust differentials

between all stages.

Fig. 192.

2. Default is Comfort. Adjust differentials as needed.

Fig. 193.

Backup Heat Differential (Droop)

A Backup Heat Differential is available for any system with 2

heating types. For example:

• Heat Pumps with any type of Backup Heat

• Radiant Heat with any type of Backup Heat

• Hot Water Fan Coil with any type of Backup Heat

The Backup Heat Differential restricts backup heat during the

following conditions:

• Normal Operation

• Manual Setpoint Changes

The options are:

Comfort – keeps temperature within 1 degree of the

setpoint.

2 to 15 °F – Backup heat is not used unless the indoor

temperature drops to the selected Backup Heat Differential.

For example, if the Backup Heat differential is set to 2 °F

(1.0 °C), the indoor temperature must be 2 °F (1.0 °C) away

from the setpoint before the backup heat turns on.

NORMAL OPERATION

When the Backup Heat Differential is set to Comfort, the

thermostat uses backup heat as needed to keep the indoor

temperature within 1 °F (0.5 °C) of the setpoint.

When the Backup Heat Differential is set to 2 °F or higher,

backup heat is not used unless the indoor temperature drops

to the Backup Heat Differential setting or the Backup Heat

Upstage Timer expires, whichever occurs first. The upstage

timer starts when the highest stage of the previous equipment

type turns on.

MANUAL TEMPERATURE CHANGE

When the Backup Heat Differential is set to Comfort, the

thermostat uses backup heat as needed to keep the indoor

temperature within 1 °F (0.5 °C) of the setpoint.

When the Backup Heat Differential is set to 2 °F or higher, if the

primary heat is making progress as expected, backup heat will

not be used to reach the new setpoint. Set to a higher number

to use less backup heat (a greater difference between the

current indoor temperature and the new setpoint is required to

turn on backup heat). See notes below.

PROGRAMMED RECOVERY

If the primary heat is making progress as expected, backup

heat will not be used to reach the setpoint of the next program

period. Backup heat is always restricted during a programmed

recovery when the Adaptive Intelligent Recovery feature is

used. See note below.

NOTE: During a programmed recovery (or when the tem-

perature setpoint is changed by the user), the

thermostat waits to turn on the backup heat

depending on system performance, load condi-

tions and how many degrees the temperature set-

point is changed. Backup heat will be used ONLY

when the temperature is not rising quickly

enough to reach the setpoint in a reasonable time.

NOTE: If the backup heat was used in the last 2 hours

because the primary heat was not able to main-

tain the setpoint, the thermostat may turn on the

backup heat earlier when the user raises the set-

point. This does NOT apply to heat pumps with

fossil fuel backup heat.

TO CHANGE BACKUP HEAT DIFFERENTIAL (DROOP)

SETTINGS

1. Select Advanced Options or Basic Options to view/adjust

Backup Heat Differential settings.

Fig. 194.

Advertising
This manual is related to the following products: