THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

68-0311—02

48

5000

What Sensors are

WIRED to your

System?

Check box on screen for each:
Indoor Air Temperature
Outdoor Air Temperature
Return Air Temperature
Discharge Air Temperature

None

Both

Yes

Wired Sensors requires an EIM (Equipment

Interface Module). This ISU is only

displayed if one of the S1-S4 terminals is

available.

Click boxes on screen to select which

sensors are wired to the S1-S4 terminals at

the EIM.

The thermostat will not display the Outdoor

Air Temperature option at ISU 5000 if a

wireless outdoor air sensor is connected.

The thermostat will not display the Indoor

Air Temperature option at ISU 5000 if 6

wireless indoor air sensors are connected.

If you have a wired Indoor Air Temperature

network (1, 4, 9 etc), the thermostat will

allow up to 5 wireless indoor air sensors.

The thermostat will not display the Return /

Discharge Air Temperature option at ISU

5000 if there is no fan in the system.

5010

Indoor

Temperature

Sensor Name

[Sensor Name]

Indoor Sensor Both

Yes

Wired Sensors requires an EIM (Equipment

Interface Module).

Enter a name (location) of the Wired Indoor

Air Temperature Sensor.

5020

What Terminals are

Wired to the Indoor

Temperature

Sensor?

None
S1
S2
S3
S4

None

Both

Yes

Wired Sensors requires an EIM (Equipment

Interface Module).

5030

Indoor

Temperature

Sensor Type

10K
20K

10K:

if ISU 1010

Application is

Residential

20K:

if ISU 1010:

Application is

Commercial

Both

Yes

Wired Sensors requires an EIM (Equipment

Interface Module).

Select 10K or 20K based on the sensor

installed. Refer to resistance values below:

C7189U1005 = 10K ohm

C7772 = 20K ohm

TR21 = 20K ohm

TR21-A = 10K ohm (IMPORTANT - the

TR21-A must be used in combination with

a TR21 sensor or another TR21-A sensor

for the thermostat to calculate the correct

indoor temperature reading).

See “Wiring guide — Wired Indoor

Sensors” beginning on page 154 for

information on the sensor type you should

select based on how the sensors are wired.

For example, you would select 20K when

you have two TR21-A (10K) sensors wired

in series.

Table 4. Installer Setup (ISU) Table. (Continued)