54

7110

Air Filter 1

Replacement

Reminder

Note: “1” is not

displayed if there is

only 1 filter.

Off

Run Time:
10, 20, 30, 45, 60, 90, 120, 150

days

Calendar:
30, 45, 60, 75 days
3, 4, 5, 6, 9, 12, 15 months

Off

Both

No

7110

Air Filter 2

Replacement

Reminder

Off

Run Time:
10, 20, 30, 45, 60, 90, 120, 150

days

Calendar:
30, 45, 60, 75 days
3, 4, 5, 6, 9, 12, 15 months

Off

Both

No

7120

Electronic Air

Cleaner Cell

Cleaning Reminder

Off

Calendar Months:
6, 7, 8, 9, 10, 11, 12 months

Off

Both

No

7120

Electronic Air

Cleaner Pre-Filter

Cleaning Reminder

Off

Calendar Months:
3, 4, 5, 6 months

Off

Both

No

7120

Electronic Air

Cleaner Post-Filter

Replacement

Reminder

Off

Calendar Months:
6, 7, 8, 9, 10, 11, 12 months

Off

Both

No

8000

Humidifier Type

None
Steam
Bypass or Fan Powered

None

Both

No

8010

Which Sensor will

be used for

Humidification

Control?

Thermostat (Internal)
Sensor Name (Remote)
Sensor Name (Remote)
Sensor Name (Remote)
Sensor Name (Remote)
Sensor Name (Remote)
Sensor Name (Remote)

(Up to 6 Remote Sensors)

Thermostat

(Internal)

Both

No

Select a sensor to control humidification

(thermostat or an optional remote sensor).

If multiple sensors are installed, you can

use a different sensor for dehumidification

control. See “Humidification control”

beginning on page 130.

Note: Humidity sensing cannot be

averaged.

8030

What Terminals are

Wired to the

Humidifier?

None
U1
U2
U3

Thermostat

defaults to the

next unused

universal

terminal (U1,

U2, U3).

Both

No

Number of Universal Outputs:

THX9321 Thermostat: U1 and U2 terminals

Equipment Interface Module (EIM): U1, U2

and U3 terminals

U1, U2, U3 are dry contacts that require

power. See “Wiring IAQ Equipment or a

Heat/Cool Stage to the Universal

Terminals” beginning on page 149.

Table 4. Installer Setup (ISU) Table. (Continued)

ISU

Number

Installer Setup

Name

Settings

Default

Residential,

Commercial

or Both

Requires

EIM

Notes

Advertising