THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

31

68-0311—02

3020

Finish With High

Cool Stage

No
Yes

No

Both

No

ISU 3010 Temperature Control Options

must be set to Advanced to view or adjust

Finish With High Cool Stage.

This ISU is only displayed when the

thermostat is set for 2 or more cool stages.

When set to Yes, this feature keeps the

high stage of the cooling equipment

running until the desired setpoint is

reached.

3021

Finish With High

Heat Stage

No
Yes

No

Both

No

ISU 3010 Temperature Control Options

must be set to Advanced to view or adjust

Finish With High Heat Stage.

This ISU is only displayed when the

thermostat is set for 2 or more heat stages.

When set to Yes, this feature keeps the

high stage of the heating equipment

running until the desired setpoint is

reached.

3030

Staging Control -

Cool Differential

Stage 2

Comfort
1.0° F to 3.5° F from setpoint (in

0.5° F increments)

Comfort

Both

No

ISU 3010 Temperature Control Options

must be set to Advanced to view or adjust

this ISU.

This ISU is only displayed when the

thermostat is set to 2 cool stages.

The indoor temperature must rise to the

selected differential setting before the

thermostat turns on the stage of cooling.

For example, if stage 2 is set to 2° F (1.0°

C), the indoor temperature must be 2° F

(1.0° C) away from the setpoint before

stage 2 turns on. When set to Comfort, the

thermostat uses the stage of cooling as

needed to keep the indoor temperature

within 1° F (0.5° C) degree of the setpoint.

3030

Staging Control -

Cool Differential

Stage 3

Comfort
1.0°F - 4.0°F from setpoint (in

0.5° F increments)

Comfort

Commercial No

ISU 3010 Temperature Control Options

must be set to Advanced to view or adjust

this ISU.

This ISU is only displayed when the

thermostat is set to 3 cool stages.

The indoor temperature must rise to the

selected differential setting before the

thermostat turns on the stage of cooling.

For example, if stage 3 is set to 2° F (1.0°

C), the indoor temperature must be 2° F

(1.0° C) away from the setpoint before

stage 3 turns on. When set to Comfort, the

thermostat uses the stage of cooling as

needed to keep the indoor temperature

within 1° F (0.5° C) degree of the setpoint.

Table 4. Installer Setup (ISU) Table. (Continued)

ISU

Number

Installer Setup

Name

Settings

Default

Residential,