THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

29

68-0311—02

2210

Backup Heat Fan

Operation

No Fan
Equipment Controls Fan
Thermostat Controls Fan

Default varies

based on

previous

selections

Both

No

This ISU is only displayed for heat pumps

when ISU 2180 Backup Heat Type is Other.

Backup Heat Fan Operation:

Electric Forced Air: Thermostat Controls

Fan

Standard Efficiency Gas Forced Air:

Equipment Controls Fan

High Efficiency Gas Forced Air: Equipment

Controls Fan

Oil Forced Air: Equipment Controls Fan

Hot Water Fan Coil: Thermostat Controls

Fan

Hot Water Radiant Heat: Not Applicable

2220

A-L/A Terminal

Setup

None
Time Of Day
Economizer
Heat Pump Failure Indication

None

Commercial No

This ISU is only displayed when ISU 1010

Application is Commercial.

Note: When the thermostat is setup for

Residential, the L/A terminal operates as

described under “Heat Pump Failure

Indication.” The L/A terminal requires no

setup for residential applications.

None: The A-L/A terminal is not used.

Time of Day: The A-L/A terminal is

energized during Occupied periods and

when the user overrides the temperature.

The terminal is de-energized during

Unoccupied periods and in Standby mode.

Economizer: The thermostat controls an

economizer module to provide ventilation

during Occupied periods and free cooling

when outdoor conditions are favorable. The

A-L/A terminal is energized during

Occupied periods and during a call for

cooling in Unoccupied periods. See

“Economizer and Time of Day (TOD)

Operation” beginning on page 126.

Notes: The economizer module determines

when outdoor conditions are favorable for

free cooling. Delta T Diagnostics is not

available when the thermostat is setup for

an Economizer.

Heat Pump Failure Indication: When 24

volts is detected on the L/A terminal

(compressor monitor), the thermostat

displays a message to alert the user when

the heat pump requires service. The L/A

terminal sends a continuous output to a

zone panel when the thermostat is set to

Emergency Heat mode. The zone panel will

not turn on the heat pump when a zone is

set to Emergency Heat mode.

Table 4. Installer Setup (ISU) Table. (Continued)

ISU

Number

Installer Setup

Name

Settings

Default

Residential,

Commercial

or Both

Requires

EIM

Notes