Zoning, Thx9321 prestige, Iaq with eim – Honeywell PRESTIGE THX9321 User Manual

Page 155: Connect power, Connected

Advertising
background image

THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

155

68-0311—02

ZONING

The following diagrams show the wiring for zoning with different IAQ equipment.

Fig. 355. Prestige IAQ thermostats with an HZ432 zone panel and no IAQ control.

C R

C R

C R

C R

RH
RC

W1/E

W2
W3

Y1
Y2

G
O

B

DS/BK

MCR34669

TRANSFORMER

R

C

M1
M4
M6

R
C

W1/E

W2
W3

Y1
Y2

G

O/B

L

DATS
DATS

OT
OT

AZ1
AZ2

ZONE 4

D

AMPER

THERMOST

A

T

EQ

UIPMENT

PO

WER

SENSORS

A

CCESSORIES

R
C

C7735A1000

DATS

A
B
C
D

THM4000R1000

WIRELESS

C

R

W

W2

Y

Y2

G

FURNACE

4

4

1

5

5

2

2

2

CONNECT

POWER

THM4000R

CONNECTED

WIRELESS SETUP

1

3

3

1

PRESTIGE THERMOSTATS CAN BE POWERED BY ANY TRANSFORMER. IN THIS EXAMPLE THEY ARE POWERED BY
THE SAME TRANSFORMER THAT POWERS THE HZ432.

THERE CAN BE UP TO 4 PRESTIGE THERMOSTATS USED WITH A SINGLE THM4000R WIRELESS ADAPTER AND HZ432
ZONE PANEL. THE THM4000R CANNOT BE USED IF THERE ARE MORE THAN 4 ZONES IN THE SYSTEM.

RH/RC JUMPER INSTALLED WHEN SINGLE HEAT/COOL TRANSFORMER IS USED.

DOTTED LINES APPLY ONLY TO MULTI-STAGE EQUIPMENT. SEE HZ432 INSTALLATION INSTRUCTIONS FOR
HEAT PUMP WIRING.

A THM4000R CANNOT BE USED WITH THE PRESTIGE THERMOSTAT IF THE THERMOSTAT IS CONTROLLING HUMIDIFICATION,
DEHUMIDIFICATION, OR VENTILATION.