Using the Equipment Test

1. Press Equipment Test on the Installer Test screen (see

Fig. 61). Turn the equipment on/off as needed and then

press Next Test to test the remaining equipment. The

time out for the Equipment Test mode is 30 minutes (if

there is no keypress for 30 minutes, the thermostat will

automatically exit the Equipment Test).

2. Run Time, Discharge, Return and Delta T data are dis-

played for heating and cooling tests (requires Discharge

and Return Air Sensors). The Discharge, Return and

Delta T are updated every 30 seconds during the test.

The Run Time counter starts over when the next stage is

turned on.

Fig. 62.

3. Discharge, Return and Delta T are updated every 30

seconds during the equipment test.

Fig. 63.

4. When that equipment test is complete, press Next Test.

5. When system testing is complete, press Exit Test.

Using the Wireless Signal Strength

Test

1. On the Installer Test screen (see Fig. 61) press Wireless

Signal Strength Test.

Fig. 64.

2. Press Test Signal Strength to begin. After a brief

pause, the thermostat will display test results.

3. A number from 5-10 means communication is good.

Fig. 65.

4. If the screen displays “No Signal,” move the thermostat

to a different location and test again.

Fig. 66.