Honeywell PRESTIGE THX9321 User Manual

Page 114

Advertising
background image

THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

68-0311—02

114

4. Select the Ventilation Fan Control. See “Ventilation Fan

Control (ISU 10060)” on page 113 for more information.

See Fig. 251.
NOTE: ISU 10060 is only displayed if the Ventilation

Type is ERV / HRV. The thermostat controls the

fan if the Ventilation Type is Fresh Air Damper.

Fig. 251.

5. If ASHRAE was selected for ISU 10050, select the Num-

ber of Bedrooms and Size of House. See Fig. 252.

Fig. 252.

6. If ASHRAE was selected for ISU 10050, enter the Equip-

ment Ventilation Rate (CFM). Be sure this setting corre-

sponds with the actual ventilator speed. This setting

determines how often the ventilation equipment will oper-

ate to meet the ASHRAE 62.2 Standard. The thermostat

will indicate the following based on the Equipment Venti-

lation Rate, Square Footage and Number of Bedrooms.

See Fig. 253.

• Provides an indication if it meets or does not meet the

ASHRAE 62.2 Standard.

• Provides% run time that is needed to meet the

ASHRAE 62.2 Standard.

Fig. 253.

7. Select a Ventilation Priority (see Fig. 254):

c.

Lockouts are Priority: The thermostat places a pri-

ority on lockouts versus the ASHRAE 62.2 ventilation

standard. The thermostat will not run ventilation dur-

ing the following lockout conditions (if configured)

unless you manually call for ventilation:

(1) Lockout Ventilation during Outdoor Conditions

(ISU 10130)

(2) Lockout Ventilation on Humidification or Dehu-

midification Calls (ISU 10140)

(3) Lockout Ventilation during “Sleep” (Residential) or

“Unoccupied” (Commercial) program periods.

Note: This option is set by the user on the Ventila-

tion screen in the Menu.

d.

ASHRAE is Priority: ASHRAE requires additional

ventilation following a long off cycle. The thermostat

meets the ASHRAE 62.2 ventilation standard by run-

ning additional ventilation when outdoor conditions

are favorable. If ASHRAE cannot be met when out-

door conditions are favorable, the thermostat will

override the outdoor lockouts and run ventilation.

When using this option, it is recommended to

increase the rate (CFM) of the ventilation equipment

to meet the ASHRAE 62.2 ventilation standard in a

shorter run time.

NOTE: ISU 10140 “Lockout Ventilation on Humidifica-

tion or Dehumidification Calls” is not an option

when you select “ASHRAE is Priority”.

The ability to lockout ventilation during the

“Sleep” or “Unoccupied” program periods is not

an option when you select “ASHRAE is Prior-

ity”.

Fig. 254.