Honeywell PRESTIGE THX9321 User Manual

Page 44

Advertising
background image

THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

68-0311—02

44

4060

Outdoor

Temperature used

with Maximum

Heat Recovery

Ramp Rate

Off
-20° F to 100° F

40° F

Commercial No

Off: The heating system will begin recovery

at the time that is scheduled.

When a Maximum Recovery Ramp Rate is

set, the thermostat will begin recovery

early to ensure the temperature is reached

at the scheduled time.

Set a Maximum Recovery Ramp Rate

based on the rate that the heating system

can recover at for a mild day in your region.

Default setting is 8° F / hour.

Set an Outdoor Temperature that is

representative of a mild day in your region

to be associated with the Maximum

Recovery Ramp Rate. The thermostat will

begin recovery at the optimal time based

on a calculated ramp rate, allowing the

system to recover on time and save energy

during changing outdoor conditions.

During recovery, the setpoint changes at a

rate in degrees per hour depending on the

outdoor temperature.

4070

Minimum Cool

Recovery Ramp

Rate

Off
1° F/hr to 20° F/hr

3° F/hr

Commercial No

Off: The cooling system will begin recovery

at the time that is scheduled.

When a Minimum Recovery Ramp Rate is

set, the thermostat will begin recovery

early to ensure the temperature is reached

at the scheduled time.

Set a Minimum Recovery Ramp Rate

based on the rate that the cooling system

can recover at for a hot day in your region.

Default setting is 3° F / hour.

If an outdoor sensor is installed, set an

Outdoor Temperature that is representative

of a hot day in your region to be associated

with the Minimum Recovery Ramp Rate.

The thermostat will begin recovery at the

optimal time based on a calculated ramp

rate, allowing the system to recover on

time and save energy during changing

outdoor conditions.

During recovery, the setpoint changes at a

rate in degrees per hour depending on the

outdoor temperature. If there is no outdoor

sensor, the Minimum Recovery Ramp

Rate is used.

Table 4. Installer Setup (ISU) Table. (Continued)

ISU

Number

Installer Setup

Name

Settings

Default

Residential,

Commercial

or Both

Requires

EIM

Notes