THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

11

68-0311—02

Selecting Return Air Temperature

Sensor Mounting Location

1. Install the Return Air Temperature Sensor on the return

duct in a location where the air is mixed well. Mount the

Return Air Temperature Sensor downstream of a Bypass

Humidifier, Dehumidifier or Ventilator. See Fig. 10–14.

Fig. 10.

Fig. 11.

Fig. 12.

Fig. 13.

MOUNT DISCHARGE

SENSOR HERE

M33074

HEAT

EXCHANGER

BLOWER

VENTILATOR

OR

DEHUMIDIFIER

MOUNT RETURN

SENSOR HERE

DOWNSTREAM OF

VENTILATOR OR

DEHUMIDIFIER

A-COIL

M33075A

HEAT

EXCHANGER

BLOWER

STEAM OR

FAN

POWERED

HUMIDIFIER

ALTERNATE MOUNTING LOCATION FOR DISCHARGE

SENSOR. WHEN SETTING THE LIMITS, BE SURE TO

CONSIDER THE AFFECT THAT THE HUMIDIFIER HAS

ON DELTA T.

MOUNT RETURN

SENSOR HERE

DOWNSTREAM OF

VENTILATOR OR

DEHUMIDIFIER

MOUNT

DISCHARGE

SENSOR HERE

ABOVE CENTER

OF A-COIL

UPSTREAM OF

STEAM OR FAN

POWERED

HUMIDIFIER

VENTILATOR

OR

DEHUMIDIFIER

M33076A

HEAT

EXCHANGER

BLOWER

MOUNT RETURN

SENSOR HERE

DOWNSTREAM OF

DEHUMIDIFIER

ALTERNATE MOUNTING LOCATION FOR DISCHARGE

SENSOR. WHEN SETTING THE LIMITS, BE SURE

TO CONSIDER THE AFFECT THAT THE DEHUMIDIFIER

HAS ON DELTA T.

MOUNT

DISCHARGE

SENSOR HERE

ABOVE CENTER

OF A-COIL

UPSTREAM OF

DEHUMIDIFIER

DEHUMIDIFIER

MOUNT RETURN

SENSOR HERE

MOUNT DOWNSTREAM

OF BYPASS HUMIDIFIER,

DEHUMIDIFIER OR

VENTILATOR

HEAT

EXCHANGER

BLOWER

VENTILATOR

OR

DEHUMIDIFIER

MOUNT

DISCHARGE

SENSOR HERE

MOUNT

DOWNSTREAM

OF BYPASS

HUMIDIFIER

BYPASS

HUMIDIFIER

M33078A