Honeywell PRESTIGE THX9321 User Manual

Page 30

Advertising
background image

THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

68-0311—02

30

3000

Changeover

Manual
Automatic

Manual:

if ISU 1010 is

Residential

Automatic:

if ISU 1010 is

Commercial

Both

No

Manual: The user must select heating or

cooling as needed to maintain the desired

indoor temperature.

Automatic: The user has the option to

select Auto for the system setting. In Auto

mode, the thermostat controls heating and

cooling equipment as needed to maintain

the desired indoor temperature.

3000

Deadband

2° F to 9° F (in 1° F increments)

3° F

Both

No

This ISU is only displayed when ISU 3000

is set to Automatic.

Deadband is the minimum separation

between heat and cool settings when the

thermostat is setup for Auto Changeover.

For example, if the deadband is set to 3° F

and the cool setpoint is 75° F, the warmest

heat setpoint allowed would be 72° F. If the

heat setpoint is adjusted above 72° F, it will

automatically adjust the cooling setpoint

higher to maintain the 3° F deadband.

When ISU 9070 (Dehumidification - Over

Cooling Limit) or ISU 9100 (High Humidity

Comfort Reset Setting) is set to 1, 2, 3, 4 or

5° F, the thermostat will not show the full

Deadband range. For example, if you set a

Deadband of 3° F and an Over Cooling

Limit of 2° F, the minimum Deadband that

you can select will be 5 F. This prevents the

heating system from turning on when the

thermostat over cools to reach the

dehumidification setting.

3010

Temperature

Control Options

Basic Options
Advanced Options
Advanced Options + PID Settings

Basic Options Both

No

Basic Options: The Installer Setup displays

basic temperature control options which

include Backup Heat Differential, Backup

Heat Upstage Timer and Outdoor

Temperature Lockouts. Note: Outdoor

Temperature Lockouts only apply to Heat

Pump applications.

Advanced Options: The Installer Setup

displays both Basic and Advanced Options.

Advanced temperature control options

include Finish With High Cool Stage, Finish

With High Heat Stage, Temperature

Differential settings between all stages and

Cycle Rate settings per stage.

Advanced Options+PID Settings: The

Installer Setup displays both Basic and

Advanced Options including PID settings

which allow you to adjust the integral,

derivative and throttling range.

Table 4. Installer Setup (ISU) Table. (Continued)

ISU

Number

Installer Setup

Name

Settings

Default

Residential,

Commercial

or Both

Requires

EIM

Notes