Honeywell PRESTIGE THX9321 User Manual

Page 51

Advertising
background image

THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

51

68-0311—02

6040

Remote Setback -

Standby Heat

Setpoint

50° F to 70° F

64° F

Commercial Yes

Remote Setback requires an EIM

(Equipment Interface Module).

During occupied periods, the occupancy

sensor tells the thermostat to go to

STANDBY (setback settings) when no one

is in the room. If someone is in the room,

then it follows the settings of the occupied

period. The occupancy sensor is ignored

during unoccupied periods.

If the thermostat is setup for non-

programmable, the occupancy sensor tells

the thermostat to go to STANDBY settings

when no one is in the room. If someone is

in the room, then it follows the settings set

by the user.

6050

What Terminals are

Wired to the Full

Drain Pan Alert Dry

Contact?

None
S1
S2
S3
S4

None

Both

Yes

Dry Contact Alerts require an EIM

(Equipment Interface Module).

6060

Full Drain Pan Alert

Dry Contact Setup

Normally Open
Normally Closed

Normally Open Both

Yes

Dry Contact Alerts require an EIM

(Equipment Interface Module).

Choose an option appropriate for the type

of device installed.

Normally Open: The Dry Contact device is

normally open and will close when the

device detects the drain pan is full.

Normally Closed: The Dry Contact device is

normally closed and will open when the

device detects the drain pan is full.

6070

What Terminals are

Wired to the Dirty

Filter Alert Dry

Contact?

None
S1
S2
S3
S4

None

Both

Yes

Dry Contact Alerts require an EIM

(Equipment Interface Module).

6080

Dirty Filter Alert

Dry Contact Setup

Normally Open
Normally Closed

Normally Open Both

Yes

Dry Contact Alerts require an EIM

(Equipment Interface Module).

Choose an option appropriate for the type

of device installed:

Normally Open: The Dry Contact device is

normally open and will close when the

device detects a dirty filter.

Normally Closed: The Dry Contact device is

normally closed and will open when the

device detects a dirty filter.

6090

What Terminals are

Wired to the Water

Leak Alert Dry

Contact?

None
S1
S2
S3
S4

None

Both

Yes

Dry Contact Alerts require an EIM

(Equipment Interface Module).

Table 4. Installer Setup (ISU) Table. (Continued)

ISU

Number

Installer Setup

Name

Settings

Default

Residential,

Commercial

or Both

Requires

EIM

Notes