1. Wire the dry contact device to S1, S2, S3, or S4 termi-

nals at the EIM.

2. Enter Installer Setup (see “Installer Options” beginning

on page 21).

3. Dry Contacts are selected at ISU 6000. Select the appro-

priate Dry Contact(s) and press Next.

Fig. 187.

4. Select the terminals wired to the Dry Contact device, and

press Next.

Fig. 188.

5. Select Normally Open or Normally Closed, and press

Next.

NOTE: For example, if a wet switch is normally open, it

will close when the device detects water. If the

wet switch is normally closed, it will open when

the device detects water.

Refer to the instructions packed with the dry

contact device to determine if it is normally

open or normally closed.

Fig. 189.

6. If you are creating a custom alert, type the alert name

into the text box and press Done. The alert name is what

appears on the Home screen when the alert is detected.

See Fig. 190. You can edit or confirm the alert name

after you enter it.

Fig. 190.

7. Type the custom alert message into the text box and

press Done. The custom alert message appears when

the orange alert button is pressed. See Fig. 191. You can

edit or confirm the alert message after you enter it.

Fig. 191.

8. Repeat steps 4–5 for the other Dry Contact, if necessary.

Staging Control

Differential Between All Stages

The thermostat provides Differential settings between all

stages. The equipment changes stages based on how far the

indoor temperature is from the setpoint. Differential settings

provide a way to balance comfort and conservation.

Heat Differential

The indoor temperature must drop to the selected differential

setting before the thermostat will turn on the stage of heating.

For example, if stage 2 is set to 2 °F (1.0 °C), the indoor

temperature must be 2 °F (1.0 °C) away from the setpoint

before stage 2 turns on. When set to Comfort, the thermostat

will use the stage of heating as needed to keep the indoor

temperature within 1 °F (0.5 °C) degree of the setpoint. The

thermostat turns on stage 2 when the capacity on stage 1

reaches 90%.