Honeywell PRESTIGE THX9321 User Manual

Page 27

Advertising
background image

THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

27

68-0311—02

2130

Backup Heat

Stages

0 - 2

1

Both

No

This ISU is only displayed when a backup

heat source is selected at ISU 2120 Backup

Heat Type.

Maximum of 2 Backup Heat stages.

2140

What Terminals are

Wired to Backup

Heat?

None
U1
U2

Default varies

based on

previous

selections

Both

No

THX9321 Thermostat Only:

This ISU is only displayed on the THX9321

thermostat when it is wired directly to the

equipment (Equipment Interface Module is

NOT used).

The thermostat can support up to 3

conventional heat stages. When there are a

total of 3 conventional heat stages, the last

stage of heat must be wired to U1 or U2.

U1 and U2 are normally open dry contacts

when configured for a stage of Heat. U1

and U2 require power from a system

transformer or a separate transformer.

2150

Backup Heat

Operation

NOT Allowed to Run with Primary

Heat
Allowed to Run with Primary Heat

NOT allowed to

run with

Primary Heat

Both

No

This ISU is only displayed when ISU 2010

Heating Equipment Type is Hot Water Fan

Coil, Electric Forced Air or Other.

When ISU 2010 Heating Equipment Type is

Hot Water Fan Coil, Electric Forced Air or

Other, you can select how the Backup Heat

operates. The thermostat can be setup to

keep the primary heat source on when it

calls for Backup Heat or the thermostat can

be setup to turn off the primary heat source

when it calls for Backup Heat.

When ISU 2010 Heating Equipment Type is

Hot Water Radiant Heat, the thermostat

keeps the Hot Water Radiant Heat on when

it calls for Backup Heat.

When ISU 2010 Heating Equipment Type is

Steam, the thermostat keeps the Steam

Heat on when it calls for Backup Heat.

2160

Backup Heat Fan

Operation

No Fan
Equipment Controls Fan
Thermostat Controls Fan

Thermostat

Controls Fan

Both

No

This ISU is only displayed for conventional

systems when ISU 2120 Backup Heat Type

is Electric Forced Air, Hot Water Fan Coil

or Other.

Backup Heat Fan Operation automatically

defaults to Equipment Controls Fan when

ISU 2120 Backup Heat Type is Standard

Efficiency Gas Forced Air, High Efficiency

Gas Forced Air or Oil Forced Air.

No Fan is only displayed when ISU 2120

Backup Heat Type is Other.

Table 4. Installer Setup (ISU) Table. (Continued)

ISU

Number

Installer Setup

Name

Settings

Default

Residential,

Commercial

or Both

Requires

EIM

Notes