THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

115

68-0311—02

8. If Percent On Time was selected for ISU 10050, select

the Ventilation Percent on Time. See Fig. 255.

Fig. 255.

9. Select the Outdoor Condition Lockouts. See “Ventilation

— Outdoor Condition Lockouts (ISU 10130)” on

page 113 for more information.
When ISU 10125 Ventilation Priority is set to Lockouts

are Priority, or ISU 10050 Ventilation Control Methods is

set to Percent On Time, the thermostat will indicate

whether this meets or may not meet the ASHRAE 62.2

Standard or the Percent On Time setting. See Fig. 256.
When ISU 10125 Ventilation Priority is set to ASHRAE is

Priority, the screen below will indicate the maximum

length of time that ventilation can be locked out over a 21

hour time period. For example, Ventilation Lockout Will

Not Exceed 12.5 hours. The length of time that ventila-

tion is locked out is limited to ensure that the ASHRAE

62.2 Ventilation Standard is met. See Fig. 256.

Fig. 256.

10. Select whether to lockout ventilation on humidification or

dehumidification calls. This feature is used to help reach

the user's desired humidity level by not allowing the ven-

tilation equipment to run during a call for humidification

or dehumidification. The thermostat will indicate whether

this meets or may not meet the ASHRAE 62.2 Standard

or the Percent On Time setting. See Fig. 257.

NOTE: ISU 10140 “Lockout Ventilation on Humidifica-

tion or Dehumidification Calls” is not an option

when you select “ASHRAE is Priority” at ISU

10125.

Fig. 257.

11. Select whether to Ventilate on High Indoor Humidity. See

“Ventilate on High Indoor Humidity (ISU 10160)” on

page 113 for more information. See Fig. 258.

Fig. 258.

Control Ventilation Level

1. Press MENU, then scroll to select Ventilation.

2. Press Setting to set the operating mode.

• Automatic: Ventilation runs as programmed by the

installer (ASHRAE or Percent On Time).

• Off: Ventilation remains off unless turned on by the

timer or from a Vent Boost Remote.

• On: Ventilation is always on.

3. Press  or  to run ventilation temporarily. The Tempo-

rary Boost (timer) setting range is 0–180 in 20 minute

increments. To turn Temporary Boost off, set to zero or

press Cancel Temporary Boost.