Honeywell PRESTIGE THX9321 User Manual

Page 35

Advertising
background image

THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

35

68-0311—02

3120

Outdoor

Temperature

Lockouts:

Compressor

Lockout / Balance

Point

Off
5° F to 60° F (in 5° F increments)

Off

(See Notes)

Both

No

ISU 3120 Compressor Lockout / Balance

Point requires an outdoor sensor.

Default is 40 F if ISU 2010 Heating

Equipment Type is Air to Air Heat Pump

and ISU 2180 Backup Type is gas or oil

forced air.

Default is Off if ISU 2010 Heating

Equipment Type is Air to Air Heat Pump

and ISU 2180 Backup Type is electric

forced air.

Default is Off if ISU 2010 Heating

Equipment Type is Geothermal Heat Pump

or Geothermal Radiant Heat.

Compressor Lockout / Balance Point is

optional for any type of heat pump (Air to

Air Heat Pump, Geothermal Heat Pump or

Geothermal Radiant Heat).

See “Heat pump with outdoor temperature

lockouts” beginning on page 100.

3120

Outdoor

Temperature

Lockouts:

Backup Heat

Lockout

Off
5° F to 65° F (in 5° F increments)

Off

Both

No

ISU 3120 Backup Heat Outdoor

Temperature Lockout requires an outdoor

sensor.

This ISU is only displayed if ISU 2010

Heating Equipment Type is Air to Air Heat

Pump, Geothermal Heat Pump or

Geothermal Radiant Heat and ISU 2190

External fossil fuel kit is set to Thermostat

Controls Backup Heat.

See “Heat pump with outdoor temperature

lockouts” beginning on page 100.

3130

Radiant Heat

Cycles Per Hour -

Stage 1

Note: “Stage 1" is

not displayed if

there is only 1

stage of Radiant

Heat.

1 to 12 CPH

3

Both

No

ISU 3010 Temperature Control Options

must be set to Advanced to view or adjust

cycle rate.

This ISU is only displayed when ISU 2010

Heating Equipment Type is Geothermal

Radiant Heat.

The thermostat automatically defaults to

the recommended setting for Geothermal

Radiant Heat (3 CPH).

Cycle rate limits the maximum number of

times the system can cycle in a 1 hour

period measured at a 50% load. For

example, when set to 3 CPH, at a 50% load,

the most the system will cycle is 3 times

per hour (10 minutes on, 10 minutes off).

The system cycles less often when load

conditions are less than or greater than a

50% load.

Table 4. Installer Setup (ISU) Table. (Continued)

ISU

Number

Installer Setup

Name

Settings

Default

Residential,

Commercial

or Both

Requires

EIM

Notes