Chapter 3 Operation

90

3.2.2 Control of Input Signal

The input signal of this controller has the input time constant of 6ms considering the prevention

of wrong operation by chattering and noise.

Therefore, input each input signal for 6ms or more

(Note)

continuously. The signal cannot be

identified if it is less than 6ms.

(Note) It is necessary to input 26ms or more for PWRT Signal of PIO Pattern 1.

[Refer to 3.2.4 Operation with Position No. Input = Operations of PIO Patterns 0 to 3 and 6.]

3.2.3 Operation Ready and Auxiliary Signals = Common to Patterns 0 to 7


[1] Emergency stop status (EMGS)

Output

PIO signal

*EMGS

Common to

Patterns 0 to 7

: Available, �: Unavailable

1) Emergency Stop Status EMGS is usually turned on and is turned off when “2.1.3 [3] Power

and Emergency Stop Circuit” is open between EMG+ and EMG- (emergency stop

condition or not connected).

2) It turns back ON if the emergency stop condition is released and the circuit is closed

between EMG+ and EMG-.

Have an appropriate safety treatment such as interlock with this signal for the host controller

(PLC, etc.).

[Caution] EMGS is different from the emergency stop output caused by a controller alarm.

Input Signal

Input Signal

Identify

Not Identify

6ms