Chapter 3 Operation

129

Judging completion of pressing operation

(1) Normal case (PIO pattern 4):

The operation monitors the torque (current limit value) in percent in “Pressing” of the position

table and turns pressing complete signal PEND ON when the load current satisfies the

condition shown below during pressing. PEND is turned ON at satisfaction of the condition if the

work is not stopped.

(Accumulated time in which current reaches pressing value [%]) – (accumulated time in which

current is less than pressing value [%]) � 255ms (Parameter No.6)

(2) Pressing operation using force sensor (PIO pattern 7):

If the pressing force during pressing operation satisfies the following condition against the

pressing force set in percent by “Pressing” in the position table, pressing complete signal PEND

is turned ON. This occurs even if the actuator does not stop.

Condition:

(Accumulated time in which pressing force enters within the range between force judgment

margin+ and force judgment margin–) � 255ms (Parameter No.6)

Current

Time

Pressing [%]

Operation

start

Approach end

Pressing start

200ms

20ms 75ms

295ms

200ms + 75ms – 20ms � 255ms

Pressing Completion (PEND Output)

Contacting work

Decrease in current due to movement of work

Time

Pressing setting value [%]

150ms

50ms

135ms

415ms

(150 + 135 + 50) – (50 + 30) � 255ms

Pressing Completion (PEND Output)

Contacting work

Work pressed back by external force

and increase in pressing force

Force judgment margin- [%]

Force judbement margin+ [%]

Pressing Force

Decreace in pressing force

due to movement of work

50ms

30ms