Chapter 3 Operation

108

[3] Pitch Feeding (relative movement = incremental feed)

Sample use

No.

Position

[mm]

Velocity

[mm/s]

Accele-

ration

[G]

Decele-

ration

[G]

Pressing

[%]

Thresh-

old

[%]

Positioning

width

[mm]

Zone+

[mm]

Zone-

[mm]

Acceleration/

Deceleration

mode

Incre-

mental

Gain

set

Stop

mode

0

1

100.00

250.00

0.20

0.20

0

0

0.10

0.00

0.00

0

0

0

0

2

25.00

250.00

0.20

0.20

0

0

0.10

0.00

0.00

0

1

0

0

(Position No.2 sets pitch feed.)

Control method

1) The method of controlling pitch feed is the same as that described in [1] Positioning except

the setting of the position table. Repeat the positioning of a specific position No.

2) For pitch feed, the position set in the position table indicates the pitch. Set the pitch

(relative moving distance = incremental moving distance) in column “Position”.

3) If the operation command is issued, the actuator moves from the current stop position by

“Position” in the position table. To perform continuous movement, repeat the operation.

The relative movement amount is calculated in ‘mm’. Therefore, there will be no cumulative

tolerable error in repeated operations.

Caution: In the pitch feed, do not perform a command with a pitch smaller than the

minimum encoder resolution (lead/encoder pulse number) or that less than

positioning accuracy repeatability.

There would be no deviation to occur even with the command because it is an

operation command to the same position as the positioning complete condition,

but the positioning control cannot be performed properly.

Velocity

1)

2)

3)

4)

4)

1)

2) 3)