13

6) Operation Mode Changeover Switch [Refer to 3.3 Operation in Pulse Train Control Mode.]

This switch is used to change from the positioner mode to the pulse train control mode or

vice versa.

Caution : For operation directed pulse trains from PLC, always set the operation

mode setting switch 11) on the front panel to “AUTO”.

7) Axis Number Setting Switch

This switch is used to set an axis number in multi-axis operation through serial

communication.

Using the SIO converter allows multiple axes to be controlled on a teaching tool such as a

PC without connection/disconnection of the connection cable connector. The SIO converter

can specify up to 16 axes with hexadecimal numbers 0 to F.

The setting of the switch is read at power-on of the controller. Changing the setting after the

power-on is invalid.

Caution : Note duplicate axis number setting, which causes a communication error

(alarm code 30C: no connection axis error) to occur and disables normal

communication.

Name

Description

1

Operation mode changeover switch

OFF : Positioner mode (including field bus specification)

ON : Pulse train control mode

(Note) This switch becomes effective at power-on.

2

Used by the manufacturer for adjustment purposes. Do

not turn it ON.

(Changing the setting of the switch is invalid even in the

power-on status.)

Point the arrow at a desired

number with a flat-head

screwdriver

Front Panel

PWR

ALM EMG

ADRS

SW

1

2

ON