Chapter 3 Operation

164

[3] Torque Limit Select (TL, TLR)

Input

Output

PIO signal

TL

TLR

This signal is used to limit the torque of the motor.

While the TL signal is ON, the actuator thrust (motor torque) can be limited to the torque set

in Parameter No.57 “Torque limit”.

With the TL signal being ON, the TLR signal (torque limiting) will turn ON when the actuator

thrust reaches the torque limit.

The TL signal is disabled during home return.

Caution:

• Do not turn the TL signal OFF while the TRL signal is ON.

An excessive deviation (accumulated pulses) may generate while torque is being limited

(TL signal is ON) (for example, the actuator may receive a load just like it receive a

pressing force in pressing operation and therefore become no longer operable). If the TL

signal is turned OFF in this condition, actuator control will start at the maximum torque

the moment the signal changes, thus causing the actuator to move suddenly or run

uncontrollably. After turning TLR signal ON, perform an operation in the reversed way to

confirm TLR signal turns OFF. After turning TLR signal ON, perform an operation in the

reversed way to confirm TLR signal turns OFF. If the condition is difficult for the reversed

movement, turn the servo OFF or clear the deviation counter (by turning DCLR ON).

[4] Deviation Counter Clear (DCLR)

Input

PIO signal

DCLR

This is the signal to clear the deviation counter that stores the specified pulse until its process

is completely finished (positioning is completed) once a command pulse is input.

It is used when the deviation is desired to be cleared after the pressing by TL signal is

complete (TLR signal ON). Once the deviation is cleared, TLR signal turns OFF and the

condition can be made as it is positioned at the point where the pressing is complete.

� �

Caution: DCLR signal is a signal that is processed at the level. Input the pulse train

while DCLR signal is on and the actuator will operate. Turn this signal ON

only when the deviation counter is cleared.