[2] Wiring and setting of safety circuit

(1) Power supply

To use safety relays and/or contactors of 24V DC specification in the safety circuit, the

control power supply should be used only for the circuit as much as possible. For example, to

supply power to the safety circuit, do not use the power supply driving our robo-cylinder

controller ACON or PCON.

It is the risk prevention treatment preparing for the cases such as the operation error of the

safety circuit caused by not enough power capacity.

(2) Specification of system I/O connector for TP adapter

Connector Name

System I/O Connector

Applicable Wire

Cable side

FMC1.5/6-ST-3.5

(Note 1)

Upper side

(EMG side) TP adapter side MCDN1.5/6-G1-3.5P26THR

Cable side

FMC1.5/6-ST-3.5

(Note 1)

Lower side

(ENB side) TP adapter side MCDN1.5/6-G1-3.5P26THR

Phoenix Contact AWG24 to 16

(0.2 to 1.25m

2

)

Pin No. Signal name

Description

1

EMG1-

2

EMG1+

Emergency stop contact 1

(30V DC or less, 100mA or less) �

3

EMG2-

4

EMG2+

Emergency stop contact 2

(30V DC or less, 100mA or less)

5

EMGIN

Emergency stop detection input

Upper side

(EMG side)

6

EMGOUT

24V power supply output for emergency

stop detection input

7

ENB1-

8

ENB1+

Enable contact 1

(30V DC or less, 100mA or less)

9

ENB2-

10

ENB2+

Enable contact 2

(30V DC or less, 100mA or less)

11

ENBIN

Enable detection input

Lower side

(ENB side)

12

ENBOUT

24V power supply output for enable

detection input

Note 1 Connectors on the cable side are attached under conditions where initial wiring has

been conducted.

In order to support each category, remove the initial wiring and wire your safety circuit.