Chapter 7

Absolute Reset and

Absolute Battery

189

7.2 Absolute Battery

An absolute battery is enclosed with the absolute type controller.

The absolute battery is used to back up the absolute data.

Connect the battery to the absolute battery connector on the front panel of the controller.

7.2.1 Absolute encoder backup specifications

Item

Specifications

Battery classification

Thionyl chloride lithium batteries

Battery manufacturer’s name

TOSHIBA HOME APPLIANCES CORP

Battery model (IAI model)

AB-5

Battery nominal voltage

3.6V

Current standard capacity

2000mAh
2 years after use (if left unused without power supply to

controller)

Reference for battery replacing timing

(Note 1)

(Ambient temperature 40�C)

4 years after use (if 50% of time with power supply to

controller)

Output of voltage drop alert signal *BALM

3.1V (Reference value)

Output of Alarm output *ALM

2.5V (Reference value)
7 days if the controller is operated continuously at 20�C.

Er

ro

r

de

te

ct

io

n

(*

1)

Warning � Reference for time suspended

after alert till alarm

2.5 days if the controller is operated continuously at

40�C.

Absolute data retaining duration at battery

replacement

15 minutes (Have the replacing work done within this

time.)

(Note 1) Replace the battery regularly.

*1 Error detection : If the voltage of the absolute battery is dropped, the error detection responding

to the voltage is held.

Voltage

PIO Signals

Alarm

3.1V (Reference value)

Voltage drop alert signal *BALM

(Note 2)

OFF

2.5V (Reference value)

Alarm signal *ALM

(Note 2)

OFF

OEE Absolute Encoder Error

Detection 2

or

OEF Absolute Encoder Error

Detection 3

(Note 2) *BALM and *ALM are the signals of active low.

After the power is supplied to the controller, they are usually on and turned OFF when an

error is detected.

Replace the battery before alarm is generated due to the lamp display by *BALM signal of

PLC.

If the alarm is generated, it will be necessary to absolute reset after the battery

replacement.