IAI America SCON-CA User Manual

Page 114

Advertising
background image

Chapter 3 Operation

104

Note 1: The completion position No. output is set to 0 during movement of the actuator.

� �

Caution:

(1) Set the period taken from entering position No. to turning CSTR ON to 6ms or larger. In spite of

6ms timer process in the PLC, commands may be input to the controller concurrently to cause

positioning to another position. Take the scanning time in the PLC into account to set a period as

2 to 4 times as the scanning time. Set the value similarly if the PLC reads the complete position.

(2) At the completion of positioning, positioning complete signal PEND is not turned ON if start

signal SCTR remains ON. If this occurs, turn CSTR OFF then PEND is turned ON immediately.

Therefore, create the sequence program so that turning PEND ON makes CSTR turned OFF

and the PLC waits for the state in which PEND is turned ON.

(3) At the positioning to the position same as that specified in the stop (complete) position number,

PEND is turned OFF once but moving signal MOVE is not turned ON.

Therefore, use PEND to turn CSTR OFF.

(4) MOVE is turned ON as soon as PEND is turned OFF and turned ON as soon as PEND is

turned ON. Accordingly, with a large positioning width being set, MOVE may be turned OFF

while the actuator is moved.

Binary data

: ON � : OFF

Command position No. PC256 PC128 PC64 PC32 PC16

PC8

PC4

PC2

PC1

Completed position No. PM256 PM128 PM64 PM32 PM16 PM8

PM4 PM2

PM1

0

1

2

3

4

5

6

7

8

9

10

•••

•••

•••

•••

•••

•••

•••

•••

•••

•••

509

510

511

Command position No.

PC1 to PC**

(PLC�Controller)

Completed position

PM1 to PM**

(Controller�PLC)

Start signal CSTR

(PLC�Controller)

Positioning Completion Signal

PEND

(Controller�PLC)

Moving Signal MOVE

(Controller�PLC)

T1�6ms

PM1 to PM**�0

(Note 1)

PM1 to PM**�0

(Note 1)

Turned OFF by

turning PEND OFF

Turned ON after

entering into

positioning width zone

Target Position