IAI America SCON-CA User Manual

Page 215

Advertising
background image

Chapter 8 I/O Parameter

205

[17] Servo ON input disable (Parameter No.21)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

21 Servo ON input disable

FPIO

0: Enabled

1: Disabled

0

This parameter defines whether the servo ON input signal is disabled or enabled.

When the servo ON input signal is disabled, the servo is turned ON as soon as the controller

power is turned ON.

Set this parameter to “1” if servo ON/OFF is not provided by PIO signals.

Set Value

Description

0

Enabled (Use the input signal)

1

Disabled (Does not use the input signal)

[18] Home Return Offset Level (Parameter No.22)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

22 Home Return Offset Level

OFST

mm

(deg)

0.00 to 9999.99

In accordance with

actuator

In this setting can set the distance from the mechanical end to the home position.

An adjustment is available for the following cases.

1) Want to match the actuator home position and the mechanical origin of the system.

2) Want to set a new home after reversing the factory-set home direction.

3) Want to eliminate a slight deviation from the previous home position generated after

replacing the actuator.

[Adjustment Process]

1) Homing execution

2) Offset check

3) Parameter setting change

4) If setting a number close to a multiple of the lead length (including home-return offset value

= 0) to the home offset value, there is a possibility to servo lock on Z-phase at absolute

reset, thus the coordinates may get shifted for the lead length.

For Absolute Type, do not attempt to set a value near a number that the lead length is

multiplied by an integral number.

Have enough margin.

After the setting, repeat home return several times to confirm that the actuator always

returns to the same home position.

Caution : If the home return offset has been changed, the soft limit parameters must

also be adjusted accordingly.

In case the there is a necessity of setting a value more than the initial setting,

contact IAI.

[19] Zone 2+, Zone 2– (Parameter No.23, No.24)

[Refer to 8.2 [1].]