Chapter 3 Operation

158

[7] Zone (ZONE1, ZONE2)

Output

PIO signal

ZONE1

ZONE2

Each of the signals turns ON when the current actuator position is inside the range specified by

the relevant parameter.

Two zones, ZONE1 and ZONE2, can be set.

When the current position of the actuator is in ZONE1, it is turned ON if it is in the range of

Parameter No.1 “Zone 1 Positive Side” and Parameter No.2 “Zone 1 Negative Side”, while is

OFF when out of the range. These signals are always enabled in the home return complete

state and not affected by the servo status or alarm status. (The ZONE2 signal turns ON/OFF

according to Parameter No.23 “Zone 2+” and Parameter No.24 “Zone 2-”.

��

Setting values and signal output range

The zone output range varies depending on the difference between the value set for the plus

side of the zone and that for the minus side.

1) Value set for plus side > value set for minus side: Output signal turn ON in the range from

the value on negative side to that on positive side, and turns OFF out of the range

2) Value set for plus side < value set for minus side: Output signal turn OFF in the range from

the value on positive side to that on negative side, and turns ON out of the range

[For Straight Slide Actuators]

[Operation of rotary actuator of multi-rotation specification in index mode]

It does not corresponds to pulse train mode.

Current

Position

Zone Signal Output

Zone Signal Output

0mm

30mm

70mm

100mm

ON

ON

ON

Set Value

Zone setting + : 70mm

Zone setting - : 30mm

Set Value

Zone setting + : 30mm

Zone setting - : 70mm