Chapter 10

Appendix

277

10.3 Example of Basic Positioning Sequence (PIO pattern 0 to 3)

This section shows an example in which a simple operation box directs SCON to move the

actuator successively to three positions on an axis.

10.3.1 I/O Assignment
























Emergency stop cancel

(Relay Circuit)

Command Position

No.1
Command Position

No.2
Command Position

No.4

Home Return

RC Start

Output

Input

RC Stop

Pause

Home Return

Completed

Position No.1

Completed

Position No.2

Completed

Position No.4

Moving

Zone1

Home Return

Completion

Operating Mode

Position Zone

Point Positioning

Completion

Operation

Preparation End
* Alarm

Emergency stop

cancel display

RC Start

Display

Pause Display

RC Stop

Display

Home Return

Display

Zone 1 Display
Position Zone

Display

Manual Mode

Display

*Pause

Start

Servo ON

Reset

PLC

S

IN0

OUT0

C
O
N

S
C
O
N

EMGRST

START

STOP

HOLD

HOME

PM1

PM2

PM4

MOVE

ZONE1

PZONE

RMDS

HEND

PEND

SV

*ALM

IN1

OUT1

IN2

OUT2

IN3

OUT3

IN4

OUT4

IN5

OUT5

IN6

OUT6

IN7

OUT7

IN8

OUT8

IN9

OUT9

IN10

OUT10

IN11

OUT11

IN12

OUT12

IN13

OUT13

IN14

OUT14

IN15

OUT15

EMRSTL

STARTL

STOPL

HOLDL

HOMEL

ZONE1L

PZONEL

RMDL

PC1

PC2

PC4

HOME

*STP

CSTR

SON

RES

Operation Box

Operation Box

“*” in codes above shows the signal of the active low. Input signal is processed with it is turned

OFF and output signal is usually ON when the power is supplied and is OFF when signal

output.