5 options, 2 pulse train input output interface, 1 pulse converter : ak-04 – IAI America SCON-CA User Manual
Page 38
Chapter 1 Specifications Check
28
1.4.2 Pulse Train Input Output Interface
Line Driver Input
Output
Specification
Input pulse equivalent to Line Driver 26C31
26C31 or equiv
Controller
Output pulse equivalent to Line Receiver 26C32
26C32 or equiv
Controller
Pulse Train
Form
Including active high and active low
1.5 Options
1.5.1 Pulse converter : AK-04
The pulse converter converts command pulses in the open collector mode to those in the
differential mode.
Use this converter if the host controller sends output pulses in the open collector mode.
Item
Specification
Input Power Supply
24V DC �10% (MAX. 50mA)
Input Pulse
O/C (Collector current MAX. 12mA)
Input Frequency
200KHz or less
Output Pulse
Differential output equivalent to 26C31 (MAX. 10mA)�
Mass
10g or less (excluding cable connector)
Accessories
37104-3122-000FL (e-CON Connector) 2 Units
Cover Color : YW
Applicable wire AWG No.24 to 26 (Less than 0.14 to 0.3mm
2
,
finished O.D. �1.0 to 1.2mm)
Caution
1) Use the pulse converter in the ambient temperature range between 0�C and 40�C.
2) The temperature increase of about 30�C occurs during operation. Accordingly,
neither install several pulse converters in close contact nor install them within a
duct. Do not install the pulse converter near other heating devices.
3) If more than one pulse converter is installed, set a pulse converter apart from another by
10mm or more.