IAI America SCON-CA User Manual

Page 213

Advertising
background image

Chapter 8 I/O Parameter

203

[10] Dynamic brake (Parameter No.14)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

14 Dynamic brake

FSTP

0 : Disabled,

1 : Enabled

1

This parameter defines whether the dynamic brake is enabled or disabled while the actuator is

at standstill.

Normally it need not be changed.

[11] Pause input disable (Parameter No.15)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

15 Pause input disable

FPIO

0 : Enabled,

1 : Disabled

0

This parameter defines whether the pause input signal is disabled or enabled.

If pause from PIO is not required, setting the parameter to “1” allows the actuator to be

operated without wiring of the pause signal input.

Set Value

Description

0

Enabled (Use the input signal)

1

Disabled (Does not use the input signal)

[12] SIO communication speed (Parameter No.16)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

16 SIO communication speed

BRSL

bps

9600 to 230400

38400

Set the SIO baud rate for the startup.

Set an appropriate value in accordance with the communication speed of the host.

One of 9600, 14400, 19200, 28800, 38400, 76800, 115200 and 230400 bps can be selected as

the communication speed.

Caution: The baud rate after the PC software is connected will be the rate of PC

software. To make effective the value set in the parameter, turn off the power

once and on it again.

[13] Minimum delay time for slave transmitter activation (Parameter No.17)

No.

Name

Symbol

Unit

Input Range

Default factory

setting

17 Minimum delay time for slave

transmitter activation

RTIM

msec

0 to 255

5

In this setting, set the time from receiving the command (received data) during the SIO

communication till the response (sent data) is returned to the host side.